Coleman P4HUE30N13006 Technical Manual page 5

Gas-fired furnaces, commercial belt- drive mid-efficiency multi-position, upflow & horizontal 130 mbh output 78 afue

Advertisement

BLOWER PERFORMANCE SCFM - UPFLOW / HORIZONTAL (WITHOUT FILTER)
TABLE 2:
VOLTAGE
230 VAC
TABLE 3:
VOLTAGE
208 VAC
+
Operation at these conditions will cause motor overload.
Operation in the shaded area may cause excessive furnace temperature rise.
NOTE: Airflow is expressed in standard cubic feet per minute.
TABLE 4: UNIT CLEARANCES TO COMBUSTIBLES (ALL SURFACES IDENTIFIED WITH THE UNIT IN A
VERTICAL POSITION
APPLICATION
TOP
UPFLOW
1
UPFLOW B-VENT
1
HORIZONTAL
1
HORIZ. B-VENT
1
NOTE: Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the
furnace jacket and building joists, studs or framing.
Unitary Products Group
Note: Data below reflects airflows with bottom return opening
MOTOR
PULLEY
0.30
040
TURNS
Closed
+
+
1 Open
3820
3687
2 Open
3575
3433
3 Open
3375
3205
4 Open
2805
2715
MOTOR
PULLEY
0.30
040
TURNS
Closed
+
+
1 Open
3674
3555
2 Open
3543
3379
3 Open
3375
3210
4 Open
3100
2919
RIGHT
LEFT
FRONT
REAR
SIDE
SIDE
6
0
0
3
3
0
0
0
6
0
0
3
3
0
0
0
EXTERNAL STATIC PRESSURE
0.50
0.60
0.70
+
+
3467
3550
3406
3240
3269
3096
2913
2996
2807
2585
2570
2351
2017
EXTERNAL STATIC PRESSURE
0.50
0.60
0.70
+
+
3383
3423
3283
3144
3213
3055
2888
3035
2850
2633
2708
2498
2226
/
FLUE
FLOOR
BOTTOM
CLOSET
6
COMBUSTIBLE
1
COMBUSTIBLE
6
COMBUSTIBLE
1
COMBUSTIBLE
036-21166 -001 REV A (0201)
,
,
.
.
INCHES
W
C
0.80
0.90
3318
3163
3066
2846
2700
2449
2293
1860
1307
--
,
,
.
.
INCHES
W
C
0.80
0.90
3242
3100
2990
2789
2673
2420
23343
1889
1724
--
ALCOVE
ATTIC
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES (SEE NOTE)
NO
YES
YES
YES (SEE NOTE)
1.00
2950
2589
2049
1026
--
1.00
2890
2555
1804
--
--
LINE CONTACT
NO
NO
5