Siemens MICROMASTER 420 Operating Instructions Manual page 105

Canopen option module
Hide thumbs Also See for MICROMASTER 420:
Table of Contents

Advertisement

Issue 01/05
Process data is sent from the drive to the network in parameter P2051 as follows:
Table 6-2
BICO connections for P2051 (PZD to CB)
Parameter
Data
2051.00
Status word 1
2051.01
Vl_velocity_demand
2051.02
User defined
2051.03
User defined
Next entries (only for MICROMASTER 440)
2051.04
Actual_torque
2051.05
Actual speed
2051.06
Modes of operation
display
NOTE
r2050 also acts as a display parameter with which the setpoints, received from the
CANopen master, can be checked. These displays always have a decimal format –
if, e.g. r2050.00 = 1150, then this would be 047EH in the hexadecimal format.
CANopen Option Module
Operating Instructions
6SE6400-5BC00-0BP0
Comment
To CANopen status word object
6041H
To CANopen vl_velocity_demand
object 6043H and to CANopen
vl_percentage_demand object 6053H
(depends on mapping selection, see
5.6 )
To CANopen free object 2803H
subindex 3
To CANopen free object 2803H
subindex 4
To CANopen object torque actual
value 6077H
To CANopen vl_control_effort in object
6044H and to vl_actual_percentage in
object 6054H
(depends on mapping selection, see
5.6 )
To CANopen modes of operation
display 6061H
Information for the CANopen master
BICO connection
BICO connection from r0052.
Parameter 700 to 6 sets the required
BICO connection
BICO connection from r0021.
Parameter 1000 to 6 sets the required
BICO connection
BICO connection can be made user-
specific
BICO connection can be made user-
specific
BICO connection from r0080.
Read from r0063 in VC and SLVC
modes. Read from r0021 in VF modes.
Default = 0
BICO connection from r0055