CFM
0.00
0.10
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
3000
381
0.26
434
0.33
3200
406
0.32
456
0.39
3400
432
0.39
478
0.46
3600
457
0.46
501
0.54
3800
483
0.54
524
0.62
4000
508
0.63
547
0.71
4200
533
0.73
570
0.82
4400
559
0.83
594
0.93
4600
584
0.95
618
1.05
4800
610
1.08
641
1.19
5000
635
1.22
666
1.33
CFM
1.00
1.10
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
3000
919 1.66
958 1.85
3200
925 1.74
965 1.94 1003 2.14 1039 2.34 1072 2.54 1104 2.73 1134 2.92
3400
931 1.82
972 2.03 1010 2.24 1047 2.45 1081 2.67 1114 2.88
3600
936 1.89
977 2.11 1016 2.33 1053 2.56 1089 2.78
3800
941 1.97
982 2.19 1022 2.42 1059 2.65 1095 2.89
4000
946 2.06
987 2.28 1027 2.51 1064 2.75 1101 3.00
4200
951 2.16
992 2.38 1031 2.61 1069 2.85
4400
958 2.27
998 2.49 1037 2.72 1074 2.96
4600
965 2.39 1004 2.61 1042 2.83
4800
974 2.53 1011 2.74 1049 2.97
5000
983 2.68 1020 2.89
LEGEND
Bhp — Brake Horsepower
ESP — External Static Pressure
NOTES:
1. Units are available with several motor hp options. Refer to
Table 2.
Table 8 — Evaporator Fan Performance — 50XCR12 Units
0.20
0.30
492
0.41
533
0.51
614
510
0.48
566
0.58
624
528
0.55
581
0.65
635
548
0.63
597
0.73
647
568
0.72
614
0.82
661
588
0.81
632
0.92
677
609
0.92
650
1.03
693
631
1.03
670
1.15
710
653
1.16
690
1.28
728
675
1.30
710
1.42
746
698
1.45
731
1.57
766
1.20
1.30
994 2.04 1029 2.22 1061 2.40 1092 2.57 1122 2.74 1149 2.91
ESP (in. wg)
0.40
0.50
0.60
0.63
674
0.77
730
0.69
681
0.83
735
0.76
689
0.90
742
0.84
699
0.98
749
0.93
710
1.06
758
1.04
722
1.17
768
1.15
736
1.28
780
1.27
751
1.40
792
1.40
767
1.53
806
1.54
783
1.68
821
1.70
801
1.84
837
ESP (in. wg)
1.40
1.50
1.60
2. Static pressure losses for any options or accessories must be
applied to external static pressure before entering the fan per-
formance table.
3. Interpolation is permitted; extrapolation is not.
4. Fan performance is based on 1 in. standard throwaway filter,
unit casing, and wet DX (direct expansion) coil losses at sea
level.
14
0.70
0.80
0.93
783
1.10
831
1.29
0.99
788
1.16
837
1.35
1.05
793
1.22
841
1.41
1.13
799
1.30
847
1.48
1.21
806
1.38
852
1.56
1.31
814
1.47
859
1.65
1.42
823
1.58
867
1.76
1.54
834
1.70
876
1.87
1.68
846
1.83
886
2.01
1.82
859
1.98
897
2.15
1.98
873
2.14
910
2.31
1.70
1.80
0.90
877 1.47
882 1.54
887 1.61
892 1.68
897 1.76
903 1.85
910 1.95
917 2.06
926 2.19
936 2.33
946 2.49
1.90