CFM
0.00
0.10
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2200
497
0.27
581
2400
542
0.35
621
2600
587
0.45
660
2800
632
0.56
701
3000
677
0.69
742
3200
723
0.84
783
3400
768
1.01
825
3600
813
1.19
867
CFM
1.00
1.10
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2200
1077 1.80 1119 1.98
2400
1099 1.97
2600
2800
3000
3200
3400
3600
LEGEND
Bhp — Brake Horsepower
ESP — External Static Pressure
NOTES:
1. Units are available with several motor hp options. Refer to
Table 2.
Table 7 — Evaporator Fan Performance — 50XCR08 Units
0.20
0.30
0.39
655
0.52
722
0.66
0.48
690
0.62
753
0.77
0.59
726
0.74
787
0.89
0.71
763
0.87
821
1.04
0.85
801
1.02
856
1.19
1.01
839
1.19
892
1.37
1.19
879
1.37
929
1.57
1.39
918
1.58
967
1.79 1013 2.00
ESP (in. wg)
1.20
1.30
ESP (in. wg)
0.40
0.50
0.60
782
0.80
839
0.95
892
812
0.92
866
1.08
917
843
1.06
895
1.22
945
875
1.21
925
1.38
974
908
1.37
957
1.56 1003 1.75 1048 1.95
942
1.56
989
1.76 1034 1.96
977
1.77 1023 1.97
1.40
2. Static pressure losses for any options or accessories must be
applied to external static pressure before entering the fan per-
formance table.
3. Interpolation is permitted; extrapolation is not.
4. Fan performance is based on 1 in. standard throwaway filter,
unit casing, and wet DX (direct expansion) coil losses at sea
level.
13
0.70
0.80
1.11
941
1.28
989
1.45 1034 1.62
1.25
966
1.42 1012 1.60 1056 1.78
1.40
992
1.58 1037 1.76 1080 1.95
1.57 1019 1.75 1063 1.95
0.90

Hide quick links: