VENTILaTION : AIRFLOW BALANCING
2nd method when adjusting the pulley :
-Close the pulley fully and count the number of turns from
fully closed position. Using table 1 determine the motor
pulley actual diameter.
-Record the fix fan pulley diameter.(DF)
-Determine the fan speed using the following formula:
rpm FAN = rpm MOTOR x D M / D F
Where : rpm MOTOR :from the motor plate or table 2
D M : from table 1
D F : from machine
Once the pulleys are adjusted and the belt checked and
tensioned, start the fan motor and record the Amps and
Voltage between the phases :
Using the measured data and table 2
-Theoretical mechanical power at the fan shaft :
x η
P
= P
meca fan
meca Motor
Transmission
x η
x η
P
= P
meca fan
elec
meca motor
= V x I x √3 x cosϕ x η
P
meca fan
This formula can be approximated in this way
P
= V x I x 1.73 x 0.85 x 0.76 x 0.9
meca fan
With the fan "rpm" and the mechanical power at the fan
shaft an operating point and the supplied airflow can be
estimated using the fan curves.
Accessories pressure drop
Table 3
-
Economiser
SIZE
Airflow
(Pa)
2900
8
020
3600
13
4300
18
3600
13
025
4500
20
5400
28
4300
11
030
5400
17
6500
24
5000
14
035
6300
23
7600
33
5800
18
040
7200
28
8600
40
6500
23
045
8100
36
9700
51
7200
28
050
9000
44
10 800
63
Transmission
x η
meca motor
Transmission
EU4
Hot

Filters

water coil (Pa)
(Pa)
S
0
22
6
32
12
43
6
32
14
46
25
63
1
29
8
43
15
59
5
37
14
56
24
77
105
0
35
6
51
12
70
3
43
10
63
18
87
113
6
51
14
76
25
105
136
CHECKING AIRFLOW AND ESP
Using the fan curves on page 25, 26, 27, the airflow, the
total pressure available (P
dynamic pressure (Pd) can now be estimated, for a specific
operating point;
The next step consist in estimating the pressure losses
across the unit.
This can be achieved using the "dirty filter pressure sensor"
and the accessories pressure drop table:
Also the pressure drop due to the duct inlet into the roof-top
unit can be taken as 20 to 30 Pa.
∆P
= ∆P
+ coil + P
filter
INT
using the results from above, the external static pressure
(ESP) can then be estimated:
- Pd - ∆P
ESP = P
TOT
Table 2
Motor Size
Nom, Speed
0,75 kW
1400 rpm
1,1kW
1425 rpm
1,5kW
1430 rpm
2,2kW
1430 rpm
3,0kW
1425 rpm
4kW
1425 rpm
5,5kW
1430 rpm
Electric
heater (Pa)
H
S
M
31
37
38
46
55
57
61
76
79
46
55
57
66
83
85
89
117
120
40
42
45
59
63
66
80
89
93
51
55
58
76
84
88
119
123
46
50
53
67
74
78
91
101
106
56
61
65
82
91
95
126
131
67
74
78
99
110
115
154
160
IOM / ROOFTOP BALTIC Series - 0803 - E Page 35
) and the corresponding
TOT
+ ∆P
Inlet
Options
INT
Cos
meca motor
0,77
0,70
0,82
0,77
0,81
0,75
0,81
0,76
0,78
0,77
0,79
0,80
0,82
0,82
Multi-
roofcurb
directional
H
(Pa)
(Pa)
40
16
23
59
24
35
81
35
50
59
24
35
88
38
55
123
55
79
47
19
18
69
29
28
96
42
41
61
25
24
91
39
38
127
58
56
57
16
23
82
25
35
111
36
51
69
20
29
100
32
45
137
46
64
82
25
35
120
39
55
166
56
80