5. Refrigerating Cycle block Diagram
INDOOR UNIT
T
1
Heat
exchanger
(Evaporator)
T
2
Refrigerating cycle temperature and pressure
Model
Operating Condition
Standard
Cooling
Max over load
Low temp
AQ24A1QC
Standard
Heating
Max over load
Deice
Standard
Cooling
Max over load
Low temp
AQ18A1QC
Standard
Heating
Max over load
Deice
Capillary tube
2-way valve
Liquid side
Gas side
3-way valve
STD Pressure
(psi)
3-WAY Valve
57-71
46-54
-
-
312-340
97-117
-
-
64-78
50-54
-
-
270-299
100-107
-
-
OUTDOOR UNIT
Check valve
Capillary tube
Heat
exchanger
(Condenser)
4-way valve
Compressor
Piping Temp.(˚F)
T1
T2
DB
46-54
80
-
-
80
-
-
67
154-169
70
-
-
80
-
-
70
50-54
80
-
-
80
-
-
67
149-158
70
-
-
80
-
-
70
Cooling
Heating
Gas leak check point
Use Temp. Condition (°F)
Indoor
Outdoor
WB
DB
WB
67
95
75
67
115
75
57
67
57
60
47
43
-
75
65
60
35
33
67
95
75
67
115
75
57
67
57
60
47
43
-
75
65
60
35
33
21