Installing The Converter In Compliance With Emc Rules - Siemens SINAMICS G120C Getting Started

Low-voltage converters. built-in devices, frame size a...c
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

3.2.2

Installing the converter in compliance with EMC rules

Rules for EMC-compliant cable routing
Preconditions
● The inverter is mounted on a metal mounting plate. The mounting plate is unpainted and
● Use shielded cables for the following connections:
Procedure
To install the inverter cables in compliance with EMC rules, proceed as follows:
1. Expose the shields of the shielded cables.
2. Place the shields on the mounting plate or on the
You have wired the inverter in an EMC-compliant fashion.
SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
has good electrical conductivity.
– Motor and motor temperature sensor
– Braking resistor
– Fieldbus
– Inputs and outputs of the terminal strip
inverter shield plate using EMC clamps.
EMC-compliant wiring shown using the
example of a frame size A inverter
Unshielded line supply cable
EMC clamps (serrated rails) on the
shield plate of the Power Module
Shielded cable to the braking resistor
EMC clamp for the cable to the
terminal strip on the shield plate of the
CU
Shielded cable to the terminal strip
Shielded motor cable
Installing
3.2 Connecting
21