6
TROUBLE
6
TROUBLE
Error code 33
Indoor temperature
sensor
Error code 34
Indoor Coil sensor
trouble
Error code 14
Outdoor temperature
sensor in trouble
Error code 1
Outdoor coil sensor
in trouble
Error code 2
Outdoor Compressor
exhaust
temperature sensor
SHOOTING
SHOOTING
Take out the red connector
sensor ,Measure the
resistance of sensor
Take out the white connector
sensor ,Meaure the
resistance of sensor
Take out the yellow
connector sensor ,Meaure
the resistance of sensor
Take
out
the
black
connector sensor ,Meaure
the resistance of sensor
Take
out
the
black
connector sensor ,Meaure
the resistance of sensor
Does the resistance
of the sensor have
the
characteristics
on part 6-3
No
Replace the the
sensor
Does the resistance
of the sensor have
the characteristic on
part 6-3 (SENSOR
PARAMETER)
No
Replace the the sensor
Error code 6
Voltage of power supply is abnormal
Is the voltage of power
supply normal of AC
198~253V?
Yes
Outdoor IPM board fault,
replace it.
Yes
Replace
the
indoor pcb board
Yes
Replace
the
outdoor board
No
Normal
protection

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

As-12ur4svete5As-18ur4sfate5As-24ur4sdbte5