Fujitsu ASU18RLF Design & Technical Manual page 28

For extra cold climate area, refrigerant r410a inverter, wall mounted type, indoor/outdoor
Hide thumbs Also See for ASU18RLF:
Table of Contents

Advertisement

¢ Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
 Function setting list
Function no.
1)
11
2)
30/31
3)
40
4)
42
5)
44
6)
46
7)
48
8)
92/93
9)
94
10)
95
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti-
mated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
11
Filter sign
Room temperature control for indoor unit sensor
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Room temperature control for wired remote controller sensor
Fixed operation mode switching
Heat insulation condition (building insulation)
Setting value
00
01
02
03
- 24 -
Functions
Setting description
Standard (400 hours)
Long interval (1,000 hours)
Short interval (200 hours)
No indication
Factory setting