Configuration example of the ET 200MP with fail-safe I/O modules
Figure 3-13
Hardware and software requirements
You use the S7-1500/ET 200MP fail-safe I/O modules:
● in S7-1500 with S7-1500 F-CPUs as of firmware version V1.7
● distributed in ET 200MP with S7-1500 F-CPUs as of firmware version V1.5 and all F-
CPUs that can be selected in the hardware catalog of the TIA Portal
The following interface modules are required for fail-safe I/O modules in ET 200MP :
● IM 155-5 PN ST, as of firmware version V3.0.0
● IM 155-5 PN HF, as of firmware version V3.0.0
● IM 155-5 DP ST, as of firmware version V3.0.0
To configure and program fail-safe I/O modules S7-1500/ET 200MP , you need:
● STEP 7 (TIA Portal) as of V13 SP1
● The option package STEP 7 Safety Advanced as of V13 SP1 + HSP0086
Automation system
System Manual, 12/2017, A5E03461182-AE
Interface module
I/O modules
Power supply (optional)
Fail-safe I/O modules
Mounting rail with integrated top-hat rail
Configuration example of the ET 200MP with fail-safe I/O modules
System overview
3.2 Configuration