Connecting the power cables of units with EMC filter +E202. Frame size R8 with top entry and exit.
Step
Instruction
11
It is recommended to make a 360
degrees grounding for the input
cable in the same way as for the
motor cable.
12
Connect the twisted shield of the
input cable to the PE busbar of
the cabinet.
13
Connect the phase conductors of
the input cable to the U1, V1 and
W1 terminals.
Fasten the shroud.
Enclosure extension layout
There are two main layouts of the enclosure extension, one for each cabling
direction. The pictures below show both the bottom and top entry/exit layouts of the
enclosure extension.