Samsung ACH1800E Technical Manual page 35

Hide thumbs Also See for ACH1800E:
Table of Contents

Advertisement

3
INSTALLATION
Control of the Remote Controller
3-2-4. Startup method by wired remote controller
G Startup in case of the "A" chamber single operation
Put on the set power.
Adjust the address of digital switch of indoor unit PCB to "0".
Put ON the option switch(DS01) N02 of wired remote controller PCB.
Put on the set power.
Press the test button of wired remote controller for more than 3 seconds.
The set is operated for 3 minutes by the forced cooling operation and the set is off after 3 minutes.
The error occurring during the test operation is displayed on the wired remote controller windows and it shall be referred to the fol-
lowing table.
G Startup of group operation
Put off the power of SET.
Adjust the addresses of digital switch of indoor unit PCB to "0"~"15", respectively.
Put on the option switch SW2 of wired remote controller PCB.
Put on the power of SET.
On the wired remote controller display, the digits "00" → "11" → "22" → are displayed up to "FF". After "FF" display, the wired
remote controller is automatically set to the preserved operation status of indoor unit of chamber "A".
If the current SET of chamber "A" is ON, put the set off by pressing the ON/OFF button.
G Only at the SET off of chamber "A", the TEST mode in enabled.
Press the TEST BUTTON of wired remote controller for more than 3 seconds.
If the SET is operating for 3 minutes through forced cooling operation, the SET is off after 2 minutes.
The Error occurring in the TEST operation displays in the wired remote controller display window and is referred to the following
table.