Fujitsu ABYA12-24LBTH Installation Manual page 14

Vrf system indoor unit floor / ceiling type
Table of Contents

Advertisement

(1) External input terminals
• Indoor unit can be Start/Stop or Emergency stop, Forced
stop by using indoor unit PCB CN6 or CN17.
Wiring methods and specifi cations
• A twisted pair cable (22AWG) should be used. Maximum
length of cable is 150 m.
* Use an external input and output cable with appropriate
external dimension, depending on the number of cables to
be installed.
• The wire connection should be separate from the power
cable line.
• Input selection
Use either one of these types of terminal according to the
application. (Both types of terminals cannot be used
simultaneously.)
• Voltage terminal ([CN6])
When a power supply must be provided at the input device
you want to connect, use the voltage terminal ([CN6]).
Load
resistance
*a
Load
resistance
*a
connected unit
*1 Make the power supply DC12 to 24V. Select a power supply
capacity with an ample surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and
1-3.
*a The allowable current is DC5~10mA. (Recommended:
DC5mA)
Provide a load resistance such that the current becomes
DC10mA or less.
Select very low current use contacts (usable at DC12V,
DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3.
Connect correctly.
When connected to voltage terminals of multiple indoor units
with a connected unit, be sure to make a branch outside the
indoor unit using a pull box, etc. as shown on below example.
Load
resistance
Load
resistance
connected unit
En-14
DC power supply
*1
12 - 24V
+
-
+
-
-
DC power
supply 12-24V
• No voltage terminal ([CN17])
When a power supply is unnecessary at the input device you
want to connect, use the no voltage terminal ([CN17]).
*c
Ch 1
connected unit
*c Select very low current use contacts (usable at DC12V,
DC1mA or less).
*d The wiring is different from voltage terminals. Be suffi ciently
careful when wiring.
When connected to no voltage terminals of multiple indoor
units with a connected unit, insulate each indoor unit with
relay, etc. as shown on below example.
When connected to multiple indoor units directly, it will cause
breakdown.
P.C.B
1
2
CN6
3
*b
Input device 1
Operation behavior
• Input signal type
The input signal type can be selected.
It is switched by Dip-sw on the indoor
unit PCB.
Dip-sw [Set 2-2]
P.C.B
OFF
ON
CN6
• When function setting is "Start/Stop" mode
In the case of "Edge" input
P.C.B
Connector
Ch1 of
CN6
CN6 or CN17
In the case of "Pulse" input
P.C.B
CN6
CN6 or CN17
*c
Ch 2
K1
K2
K3
Input device 2
Input signal type
Edge
Pulse
Input signal
Command
OFF → ON
Operation
ON → OFF
Connector
Input signal
Ch1
OFF → ON
Ch2
OFF → ON
P.C.B
1
CN17
2
3
GND
*d
P.C.B
K4
CN17
P.C.B
K5
CN17
P.C.B
K6
CN17
K1~K6: Relay
(Device for DC Current)
Edge
Pulse
The width of pulse
must be longer than
200msec.
Stop
Command
Operation
Stop