4.5

CC-Link IE Field Network function setting

4.5.1

Network number setting (Pr. 434)

Set the inverter network number in Pr. 434.
Pr.
434
Network number (CC-Link IE)

The setting range of Pr. 434 is "0 to 255", but its active range is "1 to 239".
The values out of the active range are invalid because such values cannot be transmitted to the master station.
NOTE
• The setting is applied after an inverter reset or power-ON.
4.5.2

Station number setting (Pr. 435)

Use Pr. 435 to set station number of the inverter.
Pr.
435
Station number (CC-Link IE)

The setting range of Pr. 435 is "0 to 255", but its active range is "1 to 120".
The values out of the active range are invalid because such values cannot be transmitted to the master station.
NOTE
• Use different station numbers for different devices. (If different devices have the same station number, the
communication cannot be performed properly. If an error occurs due to a duplicated number, re-assign the station
numbers, then reset the master station or the inverter power.)
• Station numbers do not have to be consecutive numbers.
• The setting is applied after an inverter reset or power-ON.
36
INVERTER SETTING
Name
Initial value
0
Name
Initial value
0
Setting range
0 to 255

Setting range
0 to 255
