Fujitsu ASU7RLF1 Service Instructions Manual page 80

Split type room air conditioner compact wall mounted / wall mounted / floor compact cassette / slim duct inverter multi
Hide thumbs Also See for ASU7RLF1:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 4
Indoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Indoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
For Compact Wall Mount, Wall Mount Type
Terminal function
Pin number
(symbol)
(wire color)
1 (Blue)
Feed back (FG)
2 (Yellow)
Speed command (Vsp)
3 (White)
Control voltage (Vcc)
4 (Black)
Ground terminal (GND)
5
No function
6 (Red)
DC voltage (Vm)
For Compact Cassette Type
Terminal function
Pin number
(symbol)
(wire color)
1
(Red)
DC voltage (Vm)
2
No function
3 (White)
Control voltage (Vcc)
4 (Black)
Ground terminal (GND)
5
No function
6
No function
7
(Yellow)
Speed command (Vsp)
8
(Brown)
Feed back (FG)
For Floor Type
Terminal function
Pin number
(symbol)
(wire color)
1 (Blue)
Feed back (FG)
2 (Yellow)
Speed command (Vsp)
3 (White)
Control voltage (Vcc)
4 (Black)
Ground terminal (GND)
5
No function
6
No function
7 (Red)
DC voltage (Vm)
For Slim Duct Type
Terminal function
Pin number
(symbol)
(wire color)
1 (Brown)
Feed back (FG)
2 (Yellow)
Speed command (Vsp)
3 (White)
Control voltage (Vcc)
4 (Black)
Ground terminal (GND)
5
No function
6 (Red)
DC voltage (Vm)
02-48