Loop Schematics/Nameplates - Emerson Fisher 3582i Instruction Manual

Positioners, electro-pneumatic converter, and valve stem position transmitter
Table of Contents

Advertisement

3582, 582i, and 3583
January 2013
Diagnostic Connections (figure 8)
FlowScannert valve diagnostics system hook‐up.
Includes connector body and body protector. If
ordered for units with gauges, a stem is also included.
Note
Part numbers are shown for recommended spares only. For part
numbers not shown, contact your Emerson Process Management sales
office.

Loop Schematics/Nameplates

This section includes loop schematics required for wiring of intrinsically safe installations. It also contains typical
approvals nameplates. If you have any questions, contact your Emerson Process Management sales office.
Figure 28. CSA Loop Schematic for Fisher 582i Converter
NOTES:
1. BARRIERS MUST BE CSA CERTIFIED WITH ENTITY PARAMETERS
 AND ARE TO BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S I.S. INSTALLATION INSTRUCTIONS.
2. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
 CANADIAN ELECTRICAL CODE, PART I.
3. FOR ENTITY INSTALLATION (I.S. AND N.I.): Vmax > Voc, Imax > Isc
 Ci + Ccable < Ca, Li + Lcable < La
GE28591 Rev A
54
Description
For 3582 pneumatic valve positioners
 For units w/gauges
  SST fittings
  brass fittings
 For units w/o gauges
  SST fittings
  brass fittings
For 3582i electro‐pneumatic valve positioners
 For units w/gauges
  SST fittings
  brass fittings
 For units w/o gauges
  SST fittings
  brass fittings
Instruction Manual
D200138X012