National Instruments NI 9411 Operating Instructions And Specifications page 21

6-channel differential digital input module
Hide thumbs Also See for NI 9411:
Table of Contents

Advertisement

Safety
Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM
or V
-to-COM ................................ 30 V max,
sup
Isolation
Channel-to-channel .................... None
Channel-to-earth ground
Continuous ........................... 30 V
Withstand ............................. 400 V
Measurement Category I is for measurements performed on
circuits not directly connected to the electrical distribution system
referred to as MAINS voltage. MAINS is a hazardous live electrical
supply system that powers equipment. This category is for
measurements of voltages from specially protected secondary
circuits. Such voltage measurements include signal levels, special
equipment, limited-energy parts of equipment, circuits powered by
regulated low-voltage sources, and electronics.
NI 9411 Operating Instructions and Specifications
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Measurement Category I
, 42.4 V
, 60 VDC
rms
pk
, verified by a 5 s
rms
dielectric withstand test
20
ni.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents