Representation Of Analog Values In The Current Output Ranges - Siemens SIMATIC S7-1500 Manual

Analog output module aq 4xu/i hf (6es7532-5nd00-0ab0)
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Representation of analog values
C.3 Representation of analog values in the current output ranges
C.3

Representation of analog values in the current output ranges

The tables below list the decimal and hexadecimal values (codes) of the possible current
output ranges.
Table C- 7
Values
>117.589 %
117.589 %
100 %
75 %
0.003617 %
0 %
-75 %
-100 %
-117.593 %
<-117.593 %
Table C- 8
Values
>117.589 %
117.589 %
100 %
75 %
0.003617 %
0 %
<0 %
46
Current output range ±20 mA
dec
hex
>32511
>7EFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
<-32512
<8100
Current output range 0 to 20 mA
dec
hex
>32511
>7EFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
<0
<0
Current output range
±20 mA
23.52 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
-723.4 nA
-15 mA
-20 mA
-23.52 mA
-23.52 mA
Current output range
0 mA to 20 mA
23.52 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
0 mA
Analog Output Module AQ 4xU/I HF (6ES7532-5ND00-0AB0)
Range
Maximum output value
Overshoot range
Rated range
Undershoot range
Minimum output value
Range
Maximum output value
Overshoot range
Rated range
Minimum output value
Manual, 03/2016, A5E36633205-AA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp

Table of Contents