Outdoor Fan Control - Fujitsu ARCG040LSTA Service Instruction

Slim duct type inverter indoor / outdoor unit, refrigerant r410a
Table of Contents

Advertisement

6. OUTDOOR FAN CONTROL

1. Outdoor Fan Motor
Following table shows the type of the outdoor fan motor. The control method is different
between AC motor and DC motor.
( Table 7 : Type of Motor )
AOCG040LBTA
2. Fan Speed
( Table 8 : Outdoor fan speed )
AOCG040LBTA
Refer to Fig.8
( Fig.8 : Outside air temperature zone selection )
Outside air
temperature
21°C
12°C
2°C
* The outdoor fan speed mentioned above depends on the compressor frequency.
(When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the
lower speed.)
* After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
as table 9 without relating to the compressor frequency.
( Table 9 : Outdoor fan speed after the defrost )
AOCG040LBTA
AC Motor
DC Motor
Zone
Cooling
Y
1050/ 870/ 720/ 530
Z
870/ 530/ 300
F
300
G
250/ 200
Outside air
temperature
Y zone
Z zone
F zone
G zone
1100rpm
1100/ 1000/ 780/ 720/ 590/ 480
19°C
10°C
0°C
01-08
Heating
Dry
530
(rpm)