Electronic Parts Troubleshooting Guide

1. Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Check the voltage of power(About AC 220V, 60Hz)
• Main power voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting
cable
• Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR1)
Check the connection housing for contacting
• Connector related to CN-POWER1, 2
• Connector related to CN-MOTOR
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Assembly Check
Items
• Power Module
(Indoor unit)
- Input Voltage
- Output Voltage
• IC04D(7805) Output
• IC01A(Reset IC)
OSC01B(8MHz)
Does "beeping" sound is made from the Indoor Unit?
NO
(About AC 220/240V, 50Hz)
Main PCB Board Operation Check
- About AC220V/240V ± 10% - Check the power voltage
- About DC12V
• DC + 5V
• Voltage of Micom No. 36
(DC +4.5V over) and Soldering condition.
Turn off Main Power
(After 10 seconds)
Turn on Main Power
Primarily, the operating condition of Micom is OK.
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting
condition of related connector
Content
-44-
YES
Remedy
• Replace Trans
• Replace IC04D
• Replace faulty parts