Message bit
If there is a condition present in the current process for a message to be
procedure
issued – for example, a tag has been reached – a bit is set by the PLC ap-
plication program in the data area for event and alarm messages. The OP
reads the data area after a configured polling time. In this way, a message is
detected as having "arrived". The bit is reset by the PLC when the condition
for issuing the message no longer exists. The message is then regarded as
having "departed".
7.1.2

Alarm messages

Acknowledging an
Due to their critical nature, alarm messages have to be acknowledged. This
alarm message
can be done manually by the operator or automatically by the PLC.
To acknowledge an alarm message manually, press this system key.
The OP displays unacknowledged alarm messages in flashing mode.
The LED assigned to the Acknowledge key (icon
After all the alarm messages have been acknowledged, the ACK LED display
changes from flashing to permanently on. Not until all the acknowledged
alarm messages have departed is the LED turned off. In this way, it is impos-
sible for you to forget an alarm message.
If several alarm messages are waiting to be displayed, after one has been
acknowledged the next one is shown, which similarly has to be
acknowledged.
If no more alarm messages are waiting to be displayed, the OP reverts to the
operating level from which it branched to the message level to display the
alarm messages.
Acknowledgement
During configuration, you can combine several alarm messages to form an
groups, group
"acknowledgement group". In this way you can acknowledge all the other
acknowledgement
alarm messages (consequential faults) in that acknowledgment group by ac-
knowledging the first alarm message – for example, the cause of the fault –
without all of them having to be output to the display on the OP (group ac-
knowledgement). You can configure up to four acknowledgment groups.
If alarm messages are not assigned to an acknowledgment group, only the
one that happens to be on the display is acknowledged if more are waiting.
Inhibiting the
There is the possibility of inhibiting the display of frequently occurring alarm
display of alarm
messages for the time being until the OP starts up as a result of a cold or
messages
warm start. Before you can inhibit the display of an alarm message, you must
have logged onto the OP with a password having a password level of at
least 8.
7-4
ACK
) also flashes.
Equipment Manual OP7, OP17
Release 04/99