5

Mounting / Installation

Configuration
5 Mounting / Installation
26
Building Technologies
Fire Safety
The alarm sounder with additional optical indicator FDS229 requires an addressed
detector base. The detector base is mounted on the wall or on the ceiling.
The device must be easily accessible for commissioning and maintenance so that it
can communicate with the detector exchanger and tester FDUD292 or the
intelligent detector tester FDUD293 via the interface (MC link).
The alarm sounder with additional optical indicator FDS229 cannot be used or
removed with the detector exchanger and tester FDUD292 or the intelligent
detector tester FDUD293!
Proceed as follows when installing:
1. Install a detector base.
-
For recess-mounted cable entry: Flat, addressable detector base FDB222
-
For surface-mounted cable entry and cable diameter
detector base FDB221 or FDB221-AA
-
For surface-mounted cable entry and cable diameter > 6 mm: Base
attachment FDB291 and addressable detector base FDB221 or
FDB221-AA
-
For applications in wet rooms: Base attachment humid FDB293 and flat,
addressable detector base FDB222 or base attachment humid FDB293
and addressable detector base FDB221/FDB221-AA
2. WARNING! Radiation of an LED in class 1M. Harmful to the eyes! Do not look
at the LED using optical instruments! Place the alarm sounder with additional
optical indicator FDS229 into the detector base and turn the alarm sounder
until it snaps in.
Wall mounting of the alarm sounder with additional optical indicator FDS229 in a detector
base FDB221
6 mm: Addressable
010095_j_en_--
2013-02-22