CHAPTER 6: ACTUAL VALUES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.

6.3.14 Flex states

ACTUAL VALUES  STATUS  FLEX STATES
 FLEX STATES
TM
There are 256 FlexState
bits available. The second line value indicates the state of the given FlexState bit.

6.3.15 Ethernet

ACTUAL VALUES  STATUS  ETHERNET
 ETHERNET
These values indicate the status of the first, second, and third Ethernet links.

6.3.16 Real time clock synchronizing

ACTUAL VALUES  STATUS  REAL TIME CLOCK SYNCHRONIZING
 REAL TIME CLOCK
 SYNCHRONIZING
actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
RTC SYNC SOURCE
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, Other, and None, where "Other" means any less precise source (SNTP,
IEC 103, IEC 104, or DNP). An actual value displays when the relay includes the IEEE 1588 software option.
The
is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
GRANDMASTER ID
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PARAM 1: Off
Off
PARAM 256: Off
Off
ETHERNET PRI LINK
STATUS: Fail
ETHERNET SEC LINK
STATUS: Fail
ETHERNET TER LINK
STATUS: Fail
RTC SYNC SOURCE:
None
GRANDMASTER ID:
0X0000000000000000
ACCURACY:
999999999 ns
PORT 1 PTP STATE:
No Signal
PORT 2 PTP STATE:
No Signal
PORT 3 PTP STATE:
No Signal
PTP - IRIG-B DELTA:
500000000 ns
Range: On, Off
Range: On, Off
Range: Fail, OK
Range: Fail, OK
Range: Fail, OK
Range: see below
Range: any 8 octet value
Range: 0 to 999,999,999 ns
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: -500,000,000 to +500,000,000 ns