Prime Condensate Trap With Water - Carrier 58UVB series Installation, Start-Up, And Operating Instructions Manual

Direct-vent upflow variable-capacity condensing gas furnace for sizes 060-120, series 100
Hide thumbs Also See for 58UVB series:
Table of Contents

Advertisement

AIR CONDITIONING
TONS (12,000 BTU/HR)
1-1/2
2
2-1/2
3
3-1/2
4
5
6
X-INDICATES AN ALLOWABLE SELECTION.
* Airflow shown in parentheses is airflow unit that the unit will deliver when setup switch SW1-5 is ON (selects 400 CFM/ton)
MODEL
080-14
080-20, 100
1.DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2.DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
Fig. 39 --- A/C or CF Airflow Selection Chart Based on 350 and 400CFM/Ton
3. Determine air conditioning tonnage used.
4. Use wiring schematic to determine proper setup position
of A/C switches. (See Fig. 23 and 39.)
NOTE: Excessive airflow caused by improper A/C switch setup
may cause condensate blowoff in cooling mode.
5. Replace main furnace door and blower access panel.
NOTE: EAC- -1 terminal is energized whenever blower operates.
HUM terminal is only energized when blower is energized in
heating.
CONTINUOUS FAN (CF) SETUP SWITCHES
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode or to select low- -cooling
airflow for two- -speed cooling units. This setup feature allows
continuous fan airflow or low- -cooling airflow to be adjusted. To
set desired continuous fan airflow or low- -cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig.
33.)
3. Determine desired continuous fan airflow or low- -cooling
airflow.
4. Use wiring schematic to determine proper setup position
of CF switches. (See Fig. 23 and 39.)
5. Replace main furnace door and blower access panel.
SETUP SWITCHES (SW1)
The furnace control has 8 setup switches that may be set to meet
the application requirements. Position these setup switches for the
appropriate requirement.
1. Remove main furnace door and blower access panel.
AIRFLOW*
060 & 080-14
(CFM)
525 (600)
700 (800)
875 (1000)
1050 (1200)
1225 (1400)
1400 (1600)
1750 (2000)
2100 (2100)
A/C OR CF AIRFLOW SELECTION CHART
BASED ON 350 CFM/TON
SIZE
060,
DEF
525
2
DEF
700
875
2
120
DEF
700
875
080-20 & 100
MODEL
MODEL
X
X
X
X
X
700
875
1050
1225
1
1050
1225
1400
1050
1225
1400
2
2. Locate setup switches on furnace control. (See Fig. 33.)
3. See Table 9 for setup switch description. (See Fig. 23.))
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SW1- -3
(Low HEAT Rise Adjust) should be in ON position. This
compensates for the increased temperature in return air resulting
from bypass.
NOTE:
If modulating dampers are used, blower motor
automatically compensates for modulating dampers.
Step 3 —Prime Condensate Trap With Water
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may
not occur. The condensate trap has 2 internal chambers
which can ONLY be primed by pouring water into the
inducer drain side of condensate trap.
1. Remove upper inducer housing drain connection cap. (See
Fig. 41.)
2. Connect field- -supplied 1/2- -in. ID tube to upper inducer
housing drain connection.
3. Insert field- -supplied funnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run
through inducer housing, overfill condensate trap, and
flow into open field drain. (See Fig. 42.)
34
120 MODEL
X
X
X
X
X
X
X
X
X
X
X
X
X
1225
1225
1750
1750
1
1750
2100
1
CAUTION
A06508

Advertisement

Table of Contents
loading

Table of Contents