Special notes on
mounting
Interior view
Siemens
Building Technologies
3.1.3
Accessories
Before fitting the accessory items shown below, the following steps must be
performed:
1. Actuator is mechanically connected to a Siemens valve.
2. Observe compatibility and choice of combinations. Refer to 2.6 (page 10).
3. Disconnect actuator, auxiliary switch from power.
Attention if AC 230 V connected danger of life!
4. Only required with actuators without fail safe function: Using the manual
adjuster, drive the actuator's stem to the fully retracted position and fix the
coupling. See "Manual operation" and "Fixing the position" (page 33).
5. To fit an auxiliary switch the housing cover must be removed and the M16
knock-out broken out.
1
3
Actuators SAS.., SAT.. for valves
Handling
2
PZ 2
No. 3
A
Plug-in space for accessory
B
Connection terminal
15 / 50
CE1P4041en
2015-05-19