Status - Delta InsightPower SNMP IPv6 User Manual

For pdc
Hide thumbs Also See for InsightPower SNMP IPv6:
Table of Contents

Advertisement

5-1-1 Status

The red and green flags represent the PDC's status. A green flag shows to indicate
normal operation. A red flag means a warning event has occurred. Refer to the fol-
lowing table for flags and the warning events they represent:
Flag
Description
Main
A warning event of the
main breaker has occurred.
X1/ X2
X1 : Transformer tempera-
ture exceeds 125 c.
X2 : Transformer tempera-
ture exceeds 150 c.
VL
Voltage phase lacking.
L1/ L2/ L3 Frequency out of range.
DSP
CAN DSP communication
error.
EPO
Emergency Power Off
initiated.
SO
System overload.
UV
Under voltage.
OC
Over current.
VT
Over voltage THD.
PF
Poor power factor.
Chapter 5
InsightPower SNMP IPv6 for PDC Web
Flag
Panel #
HT
VU
GF
FRAM
REPO
LCM
OV
UC
CT
HC
2 3
Description
A warning event of the panel
breaker has occurred.
Ambient temperature too
high.
Voltage unbalance.
Ground fault.
FRAM read/ write error.
Remote Emergency Power
Off initiated.
CAN LCM communication
error.
Over voltage.
Under current.
Over current THD.
High current.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents