The RTU Open controller can be set to communicate on
four different protocols: BACnet, Modbus, N2, and
LonWorks. Switch 3 (SW3) on the board is used to set
protocol and baud rate. Switches 1 and 2 (SW1 and SW2)
are used to set the board's network address. See Fig. 72
and 73 for protocol switch settings and address switches.
The third party connection to the RTU Open controller is
through plug J19. See Fig. 74 for wiring.
NOTE: Power must be cycled after changing the SW1- - 3
switch settings.
Refer to the RTU Open v3 Integration Guide for more
detailed information on protocols, third party wiring, and
networking.
PROTOCOL
DS8
BACnet MS/TP
Unused
(Master)
Modbus
Unused
(Slave)
N2
Unused
(Slave)
LonWorks
Unused
NOTE:
DS = DIP Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE
9600
19,200
38,400
76,800
Fig. 73 - - RTU Open Controller Address Switches
SW3 Protocol Selection
DS7
DS6
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
DS2
DS1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Fig. 72 - - RTU Open Controller SW3 DIP Switch Settings
C10815

Local Access

Wall Mounted Equipment Toucht Interface
The Equipment Touch interface is a wall mounted interface
used to connect to the RTU Open controller to access the
control information, read sensor values, and perform
maintenance. This is an accessory interface that does not
come with the RTU Open controller. Wire the Equipment
Touch interface to the RTU Open controller J13 local access
port. There are 2 password protected levels in the display
(User and Admin). See the Equipment Touch Installation
and Setup Guide for more information. See Appendix A in
the guide for navigation and screen content.
DS5
DS4
DS3
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
Fig. 74 - - Network Wiring
55
DS2
DS1
Select Baud
Select Baud
Select Baud
Select Baud
OFF
OFF
OFF
ON
C07166
C10816