Carrier 50TCQD14 Installation Instructions Manual page 32

Single package rooftop heat pump with puron (r-410a) refrigerant size 14
Hide thumbs Also See for 50TCQD14:
Table of Contents

Advertisement

Menu
Parameter
SETPOINTS
MAT SET
LOW T LOCK
DRYBLB SET
ENTH CURVE
DCV SET
MIN POS
VENTMAX
VENTMIN
ERV OAT SP
[[
EXH1 SET
EXH2 SET
Table 11 - - Menu Structure* (cont)
Parameter
Parameter
Default
Range and Increment
Value
53_F
38 to 70_F;
(12_C)
(3 to 21_C)
increment by 1
32_F
---45 to 80_F;
(0_C)
( ---43 to 27_C)
increment by 1
63_F
48 to 80_F
(17_C)
(9 to 27_C)
increment by 1
ES3
ES1, ES2, ES3, ES4, or
ES5
1100ppm
500 to 2000 ppm;
increment by 100
2.8 V
2 to 10 Vdc
2.8 V
2 to 10 Vdc
100 to 9990 cfm
increment by 10
2 to 10 Vdc
2.25 V
2 to 10 Vdc
100 to 9990 cfm
increment by 10
2 to 10 Vdc
32_F
0 to 50_F;
(0_C)
( ---18 to 10_C)
increment by 1
50%
0 to 100%;
Increment by 1
75%
0 to 100%;
Increment by 1
EXPANDED PARAMETER NAME
[
SUPPLY AIR SETPOINT
Setpoint determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
See Menu Note 2.
COMPRESSOR LOW TEMPERATURE LOCKOUT
Setpoint determines outdoor temperature when the mechanical cooling
cannot be turned on. Commonly referred to as the Compressor lockout. At
or below the setpoint the Y1---O and Y2---O will not be energized on the
controller.
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoint determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F (17_C), unit will
economize at 62_F (16.7_C) and below and not economize at 64_F
(17.8_C) and above. There is a 2_F (1.1_C) deadband.
See Menu Note 3
ENTHALPY CHANGEOVER CURVE
(Requires enthalpy sensor option)
Enthalpy boundary "curves" for economizing using single enthalpy.
See page 40 for description of enthalpy curves.
DEMAND CONTROLLED VENTILATION SETPOINT
Displays only if CO
sensor is connected. Setpoint for Demand Controlled
2
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
VENTILATION MINIMUM POSITION
Displays ONLY if a CO
sensor is NOT connected.
2
With 2---speed fan units MIN POS L (low speed fan) and MIN POS H (high
speed fan) settings are required. Default for MIN POS L is 3.2V and MIN
POS H is 2.8V.
DCV MAXIMUM DAMPER POSITION
Displays only if a CO
sensor is connected. Used for Vbz (ventilation max
2
cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you
did not have the CO
sensor.
2
If OA, MA RA and CO
sensors are connected and DCV CAL ENABLE is
2
set to AUTO mode, the OA dampers are controlled by CFM and displays
from 100 to 9990 cfm.
With 2---speed fan units VENTMAX L (low speed fan) and VENTMAX H
(high speed fan) settings are required. Default for VENTMAX L is 3.2V and
VENTMAX H is 2.8V.
DCV MINIMUM DAMPER POSITION
Displays only if CO
sensor is connected. Used for Va (ventilation min cfm)
2
setpoint. This is the ventilation requirement for less than maximum
occupancy of the space.
If OA, MA RA and CO
sensors are connected and DCV CAL ENABLE is
2
set to AUTO mode, the OA dampers are controlled by CFM and displays
from 100 to 9990 cfm.
With 2 ---speed fan units VENTMIN L (low speed fan) and VENTMIN H
(high speed fan) settings are required. Default for VENTMIN L is 2.5V
and VENTMIN H is 2.25V.
ENERGY RECOVERY VENTILATION UNIT OUTDOOR AIR TEMPERATURE
SETPOINT
Only when AUX1 O = ERV
EXHAUST FAN STAGE 1 SETPOINT
Setpoint for OA damper position when exhaust fan 1 is powered by the
economizer.
With 2---speed fan units Exh1 L (low speed fan) and Exh1 H (high speed
fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%
EXHAUST FAN STAGE 2 SETPOINT
Setpoint for OA damper position when exhaust fan 2 is powered by the
economizer. Only used when AUX1 O is set to EHX2.
With 2---speed fan units Exh2 L (low speed fan) and Exh2 H (high speed
fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%
32
Notes

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50tcqd

Table of Contents