Carrier 50TCQD14 Installation Instructions Manual page 34

Single package rooftop heat pump with puron (r-410a) refrigerant size 14
Hide thumbs Also See for 50TCQD14:
Table of Contents

Advertisement

Menu
Parameter
ADVANCED
MAT T CAL
SETUP
(cont)
OAS T CAL
OAS H CAL
RA T CAL
RA H CAL
DA T CAL
2SP FAN DELAY
CHECKOUT
DAMPER MINIMUM
[[[
POSITION
DAMPER OPEN
DAMPER CLOSE
CONNECT Y1 ---O
CONNECT Y2 ---O
CONNECT AUX1 ---O
CONNECT EXH1
Table 11 - - Menu Structure
Parameter
Parameter
Default
Range and Increment
Value
0.0_F
+/ ---2.5_F
(or C)
(+/ ---1.4_C)
1.0_F
+/ ---2.5_F
(or C)
(+/ ---1.4_C)
0% RH
+/ ---10% RH
0.0_F
+/ ---2.5_F
(or C)
(+/ ---1.4_C)
0% RH
+/ ---10% RH
0.0_F
+/ ---2.5_F
(or C)
(+/ ---1.4_C)
5 Minutes
0 to 20 minutes in
1 minute increments
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
*
(cont)
EXPANDED PARAMETER NAME
[
SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration supply air
temperature (SAT) sensor
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration outside air
temperature (OAT) sensor
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of outside air enthalpy sensor
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration return air
temperature (RA) sensor
RETURN AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of calibration return air enthalpy
sensor
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration discharge air
temperature (DAT) sensor
nd
TIME DELAY ON 2
STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try to
satisfy the call for second stage cooling before the first stage mechanical
cooling is enabled.
The checkout for the damper minimum positions is based on the system.
See Table 12.
Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure
you pause in this mode to allow for exhaust contacts to energize due to the
delay in the system.
Positions damper to the fully closed position
Closes the Y1---O relay (Y1---O).
See CAUTION on page 41.
Closes the Y2---O relay (Y2---O)
See CAUTION on page 41.
Energizes the AUX1---O output. If AUX1---O setting is:
S NONE --- not action taken
S ERV --- 24 Vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are good for ERV operation.
S SYS --- 24 Vac out. Issues a system alarm.
Closes the power exhaust fan 1 relay (EXH1)
34
Notes
[[