The ML193UH can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE - In Non-Direct Vent installations, combustion air
is taken from indoors and flue gases are discharged out-
doors. In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according
to tables 4 and 5. Count all elbows inside and outside the
home. Table 4 lists the minimum vent pipe lengths per-
mitted. Table 5 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination. Refer to table 8.
In some applications which permit the use of several dif-
ferent sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox' Application Department for assis-
tance in sizing vent pipe in these applications.
NOTE - The exhaust collar on all models is sized to ac-
commodate 2" Schedule 40 vent pipe. In horizontal ap-
plications, any transition to exhaust pipe larger than 2"
must be made in vertical runs of the pipe. Therefore a 2"
elbow must be added before the pipe is transitioned to
any size larger than 2". This elbow must be added to the
elbow count used to determine acceptable vent lengths.
Contact the Application Department for more information
concerning sizing of vent systems which include multiple
pipe sizes.
Horizontal Installation Offset Requirements
Exhaust Pipe
Horizontal
Gas Furnace
12" ma x
of straight pip e
NOTE -
ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm)
of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
FIGURE 22
TABLE 4
MINIMUM VENT PIPE LENGTHS
ML193UH MODEL
045, 070, 090, 110
135
12" Min .
MIN. VENT LENGTH*
15 ft. or 5 ft plus 2 elbows or
10 ft plus 1 elbow
Use the following steps to correctly size vent pipe diam-
eter.
1
2
3
4
5
6
7
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
Page 17
Piping Size Process
What is the
furnace capacity?
045, 070, 090,
110 or 135?
Which style termination
being used?
Standard or concentric?
See table 3.
Which needs
most elbows?
Intake or
exhaust?
How many elbows?
Count all elbows inside
and outside house.
Desired pipe size?
2", 2-1/2", 3"
What is the altitude of
the furnace installation?
Use table 5 or 6 to find
max intake or exhaust pipe
length. Includes all vent
pipe and elbows inside
and outside the house.
FIGURE 23
IMPORTANT
IMPORTANT