Use the following method to install the kit on the CTR, referring to Figure 2-5:
1
2
3
4
5
Figure 2-5
Grounding the CTR
CTR
Install the ¼" stainless steel hex bolt, stainless steel flat washer and the
stainless steel internal tooth washer through one of the four holes in the
CTR. (Refer to Figure 2-5 for the hole location.)
Install a stainless steel internal tooth washer, stainless steel flatwasher
and the 1/4" nut onto the assembly installed in Step 1.
Repeatedly tighten and loosen the fastener assembly, rotating the
internal tooth lock washer, until the powder coating is scraped off and
the bare metal is exposed. Repeat this procedure if required.
Discard the internal tooth washer used to remove the powder coating.
Using new stainless steel internal tooth washers, assemble the complete
ground cable connection, as per Figure 2-5.
Grounding and Surge Protection 2-9
Hex head
capscrew
Flat washer
Cable (not provided)
Internal tooth
Lock washer
Hex nut