Section 4
INSTALLATION
Figure 4-1 Service Air Piping with Aftercooler and Optional Air Dryer (Typical)

4.4 COUPLING ALIGNMENT CHECK

No coupling alignment is required.

4.5 FLUID LEVEL CHECK

The air compressor is also supplied with the proper
amount of fluid. However, it is necessary to check
the fluid level at installation. The level is checked by
looking at the sight glass located near the sump. If
the sump is properly filled, fluid should be visible in
the sight glass while compressor is in run mode.
The maximum fluid level is the level of the filler port.
4.6
ELECTRICAL
ELECTRO- -MECHANICAL
Interior electrical wiring is performed at the factory.
Required customer wiring is minimal, but should be
done by a qualified electrician in compliance with
OSHA, National Electrical Code, and/or any other
applicable State, Federal and local electrical codes
concerning isolation switches, fused disconnects,
etc. Sullair provides a wiring diagram for use by the
installer.
22
PREPARATION- -STANDARD
NOTE
Customer must provide electrical supply power
disconnect within sight of machine.
A few electrical checks should be made to help as-
sure that the first start--up will be trouble--free.
WARNING
!
Lethal shock hazard inside. Disconnect all power
at source before opening or servicing.
1. Check incoming voltage. Be sure that compres-
sor is wired for the correct incoming voltage.
2. Check starter for correct size, proper overload
relay, and heaters.
3. Check all electrical connections for tightness.
4. "DRY RUN" the electrical controls by disconnect-
ing the three (3) motor leads from the starter. En-
ergize the control circuits by pressing the "I"
START push button and check all protective de-
vices to be sure that they will de--energize the
starter coil when tripped.