Mitsubishi Electric FR-A820-00046 Instruction Manual page 591

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
● Calibration parameter according to the terminal 4 function
Pr. 858
setting
0
(initial
value)
1
4
9999
Tab. 5-161: Terminal 4 functional calibration parameter
Adjustment of the bias and gain for stall prevention operation level is done by Pr. 148 "Stall
prevention level at 0 V input" and Pr. 149 "Stall prevention level at 10 V input".
Change the torque at maximum analog input. (C18 (Pr. 920), C40 (Pr. 933))
To only change the torque setting (gain) of the maximum analog input voltage (current), set to C18
(Pr. 920), C40 (Pr. 933).
FR-A800
Terminal function
Bias setting
C5 (Pr. 904) "Terminal 4 frequency setting
Frequency (speed)
bias frequency"
command/
C6 (Pr. 904) "Terminal 4 frequency setting
Speed limit
bias"
C38 (Pr. 932) "Terminal 4 bias command
Magnetic flux
(torque)"
command
C39 (Pr. 932) "Terminal 4 bias (torque)"
Stall prevention
C38 (Pr. 932) "Terminal 4 bias command
(torque)"
operation level
/
torque limit
C39 (Pr. 932) "Terminal 4 bias (torque)"
No function
(T) Multi-Function Input Terminal Parameters
Calibration parameter
Gain setting
Pr. 126 "Terminal 4 frequency setting gain
frequency"
C7 (Pr. 905) "Terminal 4 frequency setting
gain"
C40 (Pr. 933) "Terminal 4 gain command
(torque)"
C41 (Pr. 933) "Terminal 4 gain (torque)"
C40 (Pr. 933) "Terminal 4 gain command
(torque)"
C41 (Pr. 933) "Terminal 4 gain (torque)"
5 - 411

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents