Outdoor Air Enthalpy Control - Bryant 580J*04A Installation Instructions Manual

580j legacy series single package rooftop with gas heat/electric cooling sizes 04, 05, 06, 07
Table of Contents

Advertisement

IF THIS LED IS ON...
Power
Rx
Tx
DO#
IF THIS LED IS ON...
2 Flashes Per Second
2 Flashes Per Second
2 Flashes Per Second
2 Flashes Per Second
2 Flashes Per Second
5 Flashes Per Second
5 Flashes Per Second
7 Flashes Per Second
14 Flashes Per Second
On
NOTE: Refer to the RTU Open Multi-Protocol Controller
Controls, Start-Up, Operation and Troubleshooting manual
for complete configuration of RTU Open, operating se-
quences and troubleshooting information. Contact your
Bryant applications engineer for details on configuration
and troubleshooting of connected networks.
OUTDOOR
AIR
(PN: 33CSENTHSW) — The enthalpy control is avail-
able as a field-installed accessory to be used with the
EconoMi$er
®
2 damper system. The outdoor air enthalpy
sensor is part of the enthalpy control. (The separate field-in-
stalled accessory return air enthalpy sensor (33CSENTSEN)
is required for differential enthalpy control (see Fig. 61).
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory harness
and connect the gray lead labeled "ESL" to the terminal labeled
"LOW". See Fig. 61. Connect the enthalpy control power input
terminals to economizer actuator power leads RED (connect to
24V) and BLK (connect to GND).
Enthalpy
Switch
24V
GND
LOW
Fig. 61 — Enthalpy Switch (33CSENTHSW)
Connections
The outdoor enthalpy changeover setpoint is set at the en-
thalpy controller.
Differential Enthalpy Control — Control is provided by sens-
ing and comparing the outside air and return air enthalpy con-
ditions. Install the outdoor air enthalpy control as described
above. Add and install a return air enthalpy sensor.
Return Air Enthalpy Sensor (33SENTSEN) — The sensor is
mounted in the return-air section of the economizer. The return
air sensor is wired to the enthalpy controller (33CSENTHSW).
See Fig. 62.
Table 26 — LEDs
(The LEDs on the RTU Open show the status of certain functions)
THE STATUS IS...
RTU Open has power
RTU Open is receiving data from the network segment
RTU Open is transmitting data over the network segment
The digital output is active
The Run and Error LEDs indicate control module and network status
THE STATUS IS...
Off
2 flashes, alternating with Run LED
3 flashes, then off
4 flashes, then pause
On
On
Off
7 flashes per second, alternating with Run LED
14 flashes per second, alternating with Run LED
On
ENTHALPY
CONTROL
RED
PL6-1 (24-V)
BLK
PL6-4 (COM)
GRA
7
CTB ECON
(P'LINK: to J4-2) or
(RTU Open: to J2-6)
FACTORY WIRING HARNESS
Status is...
Normal
Five minute auto-restart delay after system error
Control module has just been formatted
Two or more devices on this network have the same
ARC156
Network address
Exec start-up aborted, Boot is running
Firmware transfer in progress, Boot is running
Ten second recovery period after brownout
Brownout
Failure. Try the following solutions:
Turn RTU Open off, then on
Format RTU Open
Download memory to RTU Open
Replace RTU Open
24V
– 4-20
MAIN
GND
+ VDC
OUT
LOW
OUTSIDE AIR
ENTHALPY SWITCH
+ 24-36
VDC IN
– 4-20 MAIN
OUT
Fig. 62 — Outside and Return Air Enthalpy Sensor
SMOKE DETECTORS — Smoke detectors are available as
factory-installed options on 580J models. Smoke detectors may
be specified for Supply Air only or for Return Air without or
with economizer or in combination of Supply Air and Return
Air. All components necessary for operation are factory-pro-
vided and mounted. The unit is factory-configured for immedi-
ate smoke detector shutdown operation; additional wiring or
modifications to unit terminal board may be necessary to com-
plete the unit and smoke detector configuration to meet project
requirements.
Units equipped with factory-optional Return Air smoke de-
tectors require a relocation of the sensor module at unit installa-
tion. See Fig. 63 for the as shipped location.
45
RED
PL6-1 (24-V)
BLK
PL6-4 (COM)
CTB ECON
GRA
7
(P'LINK: to J4-2) or
(RTU Open: to J2-6)
RETURN AIR
ENTHALPY
SENSOR
Wiring