Measuring Ranges - Siemens 6ES7134-4JB00-0AB0 Manual

Distributed i/o 2ai tc st analog electronic module
Table of Contents

Advertisement

4.3

Measuring ranges

4.3.1
Measuring ranges for thermocouples
Introduction
The following tables contain the digitized analog values for the measuring ranges of the
analog input modules.
Since the binary representation of the analog values is always the same, these tables only
compare the measuring ranges with the units.
Measuring range for thermocouple: Type B
Table 4-3
Type B in °C
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
Manual, 04/2007, A5E01076883-01
SIMATIC S7 format: Type B measuring range in °C
Decimal
> 2070,0
32767
2070,0
20700
:
1820,1
18201
1820,0
18200
:
0,0
-0,1
:
-120,0
-1200
< -120,0
-32768
Units
Hexadecimal
7FFF
50DC
:
4719
4718
:
0
0000
-1
FFFF
:
FB50
8000
Analog value representation
4.3 Measuring ranges
Overflow
H
H
:
Overrange
H
H
:
Nominal range
H
H
:
Underrange
H
Underflow
H
Range
19