Parameters
2.1
Parameters
Table 2-1
Parameters for analog input module
2AI TC ST
Group diagnostics (parameter
assignment error, internal error)
Diagnostics: Overflow/underflow
Diagnostics: Wire-break check
Smoothing
Comparison point
Reference junction number
Type/range of measurement
Only with thermocouples. A parameter assignment error occurs when the wire break diagnosis is enabled in the voltage
*
measuring range. The module does not start up.
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
Manual, 04/2007, A5E01076883-01
Range of values
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
*
Enable
•
None
•
Weak
•
Medium
•
Strong
•
None
•
RTD
•
None
•
1 to 8
•
(in the case of the IM151-1
STANDARD and IM151-1 FO
STANDARD)
1
•
(in the case of the IM151-1
BASIC, IM151-1 COMPACT,
IM151-1 HIGH FEATURE)
Deactivated
•
Voltage ± 80 mV
•
TC-EL Type T (Cu-CuNi)
•
TC-EL Type K (NiCr-Ni)
•
TC-EL Type B (PtRh-PtRh)
•
TC-EL Type N (NiCrSi-NiSi)
•
TC-EL Type E (NiCr-CuNi)
•
TC-EL Type R (PtRh-Pt)
•
TC-EL Type S (PtRh-Pt)
•
TC-EL Type J (Fe-Cu-Ni)
•
TC-EL Type L (Fe-Cu-Ni)
•
Default setting
Disable
Disable
Disable
None
None
None
TC-EL Type K (NiCr-
Ni)
2
Applicability
Module
Module
Channel
Channel
Channel
Module
Channel
13