Parameters - Siemens 6ES7134-4JB00-0AB0 Manual

Distributed i/o 2ai tc st analog electronic module
Table of Contents

Advertisement

Parameters

2.1
Parameters
Table 2-1
Parameters for analog input module
2AI TC ST
Group diagnostics (parameter
assignment error, internal error)
Diagnostics: Overflow/underflow
Diagnostics: Wire-break check
Smoothing
Comparison point
Reference junction number
Type/range of measurement
Only with thermocouples. A parameter assignment error occurs when the wire break diagnosis is enabled in the voltage
*
measuring range. The module does not start up.
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
Manual, 04/2007, A5E01076883-01
Range of values
Disable
Enable
Disable
Enable
Disable
*
Enable
None
Weak
Medium
Strong
None
RTD
None
1 to 8
(in the case of the IM151-1
STANDARD and IM151-1 FO
STANDARD)
1
(in the case of the IM151-1
BASIC, IM151-1 COMPACT,
IM151-1 HIGH FEATURE)
Deactivated
Voltage ± 80 mV
TC-EL Type T (Cu-CuNi)
TC-EL Type K (NiCr-Ni)
TC-EL Type B (PtRh-PtRh)
TC-EL Type N (NiCrSi-NiSi)
TC-EL Type E (NiCr-CuNi)
TC-EL Type R (PtRh-Pt)
TC-EL Type S (PtRh-Pt)
TC-EL Type J (Fe-Cu-Ni)
TC-EL Type L (Fe-Cu-Ni)
Default setting
Disable
Disable
Disable
None
None
None
TC-EL Type K (NiCr-
Ni)
2
Applicability
Module
Module
Channel
Channel
Channel
Module
Channel
13