York Predator ZF120 Technical Manual page 25

Zf series 6.5 - 12.5 ton 60 hertz
Hide thumbs Also See for Predator ZF120:
Table of Contents

Advertisement

ZF120 (10 Ton) (Continued)
Air on
Evaporator Coil
Total
1
Capacity
WB
CFM
(MBh)
(°F)
77
117.2
72
106.1
2500
67
95.0
62
85.5
77
120.1
72
108.7
3000
67
97.4
62
87.5
57
90.8
77
122.9
72
111.3
3500
67
99.7
62
89.6
57
93.0
77
125.8
72
113.9
4000
67
102.0
62
91.7
57
95.1
72
115.9
67
103.8
4500
62
93.3
57
96.8
72
117.9
67
105.6
5000
62
95.0
57
98.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
115°F
11.2
54.3
43.9
33.2
10.8
74.7
63.9
53.2
10.4
95.0
84.0
73.3
10.1
85.5
85.5
81.6
11.2
64.1
47.2
34.5
10.9
80.7
68.1
55.4
10.5
97.4
88.9
76.3
10.2
87.5
87.5
87.5
10.3
90.8
90.8
87.8
11.3
73.9
50.5
35.9
10.9
86.8
72.2
57.6
10.6
99.7
93.9
79.3
10.3
89.6
89.6
93.5
10.4
93.0
93.0
91.3
11.4
83.7
53.8
37.2
11.0
92.9
76.3
59.8
10.6
102.0
98.8
82.3
10.4
91.7
91.7
99.5
10.5
95.1
95.1
94.7
11.1
99.2
81.4
63.6
10.7
103.8
102.2
87.6
10.4
93.3
93.3
97.2
10.5
96.8
96.8
96.6
11.1
105.5
86.5
67.4
10.7
105.6
105.6
92.8
10.5
95.0
95.0
95.0
10.6
98.5
98.5
98.5
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
75
70
65
-
-
-
104.6
42.5
-
-
94.9
62.6
51.8
-
85.2
70.9
60.1
49.4
76.3
-
-
-
106.6
42.7
-
-
96.7
63.6
51.0
-
86.8
74.9
62.2
49.6
77.7
75.2
62.5
49.8
83.7
-
-
-
108.6
43.0
-
-
98.5
64.7
50.1
-
88.4
78.9
64.3
49.7
79.2
76.7
62.1
47.5
85.3
-
-
-
110.6
43.2
-
-
100.3
65.7
49.2
-
90.0
82.9
66.4
49.8
80.6
78.2
61.6
45.1
86.9
45.8
-
-
102.2
69.8
52.0
-
91.7
79.4
61.6
43.8
82.2
78.8
61.0
43.2
88.5
48.4
-
-
104.2
73.8
54.7
-
93.5
75.9
56.8
37.8
83.7
79.4
60.4
41.3
90.2
5167798-YTG-J-0218
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
125°F
12.1
64.4
42.9
31.5
11.6
74.8
64.0
53.3
11.1
85.2
85.2
75.2
10.8
76.3
76.3
76.3
12.3
71.1
45.8
31.5
11.7
78.9
66.3
53.7
11.2
86.8
86.8
75.9
10.9
77.7
77.7
77.7
11.0
83.7
83.7
83.7
12.4
77.9
48.7
31.5
11.8
83.1
68.6
54.0
11.3
88.4
88.4
76.5
11.0
79.2
79.2
79.2
11.1
85.3
85.3
85.2
12.5
84.6
51.6
31.5
11.9
87.3
70.8
54.3
11.4
90.0
90.0
77.2
11.1
80.6
80.6
80.6
11.2
86.9
86.9
85.7
12.0
93.1
75.4
57.7
11.5
91.7
91.7
82.0
11.1
82.2
82.2
82.2
11.3
88.5
88.5
87.9
12.1
98.9
80.0
61.2
11.5
93.5
93.5
86.9
11.2
83.7
83.7
83.7
11.3
90.2
90.2
90.2
75
70
65
-
-
-
42.6
-
-
64.5
53.8
-
70.2
59.4
48.7
-
-
-
41.0
-
-
63.2
50.6
-
72.6
60.0
47.3
72.1
59.4
46.8
-
-
-
39.4
-
-
62.0
47.4
-
75.0
60.5
45.9
70.6
56.1
41.5
-
-
-
37.8
-
-
60.7
44.2
-
77.4
61.0
44.5
69.2
52.7
36.2
40.1
-
-
64.4
46.7
-
71.2
53.5
35.8
70.3
52.6
34.9
42.3
-
-
68.0
49.2
-
64.9
46.0
27.2
71.4
52.5
33.7
25