York Predator ZF120 Technical Manual page 24

Zf series 6.5 - 12.5 ton 60 hertz
Hide thumbs Also See for Predator ZF120:
Table of Contents

Advertisement

5167798-YTG-J-0218
ZF120 (10 Ton)
Air on
Evaporator Coil
Total
1
Capacity
WB
CFM
(MBh)
(°F)
77
165.2
72
149.2
2500
67
133.2
62
121.8
77
170.9
72
154.3
3000
67
137.7
62
125.9
57
120.2
77
176.6
72
159.4
3500
67
142.3
62
130.1
57
124.2
77
182.2
72
164.5
4000
67
146.8
62
134.3
57
128.2
72
168.0
67
149.9
4500
62
137.1
57
130.9
72
171.4
67
153.0
5000
62
139.9
57
133.5
77
142.4
72
128.6
2500
67
114.8
62
103.8
77
147.0
72
132.8
3000
67
118.6
62
107.1
57
105.0
77
151.6
72
137.0
3500
67
122.3
62
110.5
57
108.3
77
156.2
72
141.1
4000
67
126.0
62
113.9
57
111.6
72
143.3
67
127.9
4500
62
115.6
57
113.3
72
145.5
67
129.9
5000
62
117.4
57
115.1
24
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
75°F
7.4
67.4
56.3
45.3
7.5
84.0
72.9
61.8
7.5
100.5
89.4
78.4
7.5
121.8
105.9
93.0
7.4
76.4
63.0
49.7
7.4
94.5
81.2
67.8
7.4
112.6
99.3
86.0
7.5
125.9
115.4
102.0
7.4
120.2
120.2
109.7
7.4
85.3
69.7
54.1
7.4
105.0
89.5
73.9
7.4
124.8
109.2
93.6
7.5
130.1
124.8
111.1
7.4
124.2
124.2
119.4
7.3
94.3
76.4
58.6
7.4
115.6
97.7
79.9
7.4
136.9
119.1
101.2
7.4
134.3
134.3
120.1
7.4
128.2
128.2
129.1
7.4
124.0
104.8
85.6
7.4
144.9
127.7
108.5
7.4
137.1
137.1
130.0
7.4
130.9
130.9
131.3
7.4
132.5
111.9
91.3
7.4
153.0
136.3
115.7
7.5
139.9
139.9
139.9
7.4
133.5
133.5
133.5
95°F
9.2
58.1
47.3
36.6
9.1
74.5
63.7
53.0
9.0
90.9
80.2
69.4
8.8
103.8
100.4
83.0
9.2
66.1
53.4
40.7
9.1
84.3
71.6
58.9
9.0
102.5
89.8
77.1
8.9
107.1
104.9
92.2
8.9
105.0
105.0
94.1
9.3
74.1
59.4
44.7
9.2
94.2
79.5
64.8
9.1
114.2
99.5
84.8
8.9
110.5
109.4
101.4
8.9
108.3
108.3
103.5
9.3
82.1
65.4
48.8
9.2
104.0
87.3
70.6
9.1
125.9
109.2
92.5
8.9
113.9
113.9
110.5
8.9
111.6
111.6
112.9
9.2
111.4
93.4
75.3
9.1
127.9
116.7
98.6
9.0
115.6
115.6
114.0
9.0
113.3
113.3
114.0
9.2
118.9
99.4
80.0
9.1
129.9
124.2
104.8
9.0
117.4
117.4
117.4
9.0
115.1
115.1
115.1
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
75
70
65
-
-
-
153.8
50.8
-
-
138.9
67.3
56.3
-
124.0
82.0
70.9
59.8
112.8
-
-
-
159.0
54.5
-
-
143.5
72.7
59.3
-
128.1
88.7
75.4
62.1
116.5
96.3
83.0
69.7
112.6
-
-
-
164.1
58.3
-
-
148.2
78.0
62.4
-
132.3
95.5
79.9
64.3
120.3
103.8
88.2
72.6
116.3
-
-
-
169.2
62.0
-
-
152.8
83.3
65.5
-
136.4
102.2
84.4
66.5
124.1
111.3
93.4
75.5
119.9
66.4
-
-
155.6
89.2
70.0
-
138.9
110.8
91.5
72.3
126.3
112.1
92.9
73.7
122.1
70.7
-
-
158.4
95.1
74.5
-
141.4
119.3
98.7
78.1
128.6
113.0
92.4
71.8
124.3
-
-
-
129.8
42.3
-
-
117.4
58.7
48.0
-
104.9
72.3
61.5
50.8
94.6
-
-
-
133.5
46.2
-
-
120.8
64.4
51.7
-
108.0
79.5
66.7
54.0
97.3
81.4
68.7
56.0
97.9
-
-
-
137.3
50.1
-
-
124.1
70.1
55.4
-
111.0
86.7
72.0
57.3
100.1
88.8
74.1
59.4
100.6
-
-
-
141.0
54.0
-
-
127.5
75.8
59.1
-
114.0
93.9
77.2
60.5
102.8
96.2
79.5
62.8
103.4
57.2
-
-
129.6
80.6
62.5
-
115.9
95.9
77.8
59.7
104.5
95.9
77.8
59.7
105.1
60.5
-
-
131.7
85.3
65.8
-
117.7
97.9
78.4
59.0
106.2
95.6
76.1
56.7
106.8
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
85°F
8.3
62.7
51.8
40.9
8.3
79.2
68.3
57.4
8.2
95.7
84.8
73.9
8.2
112.8
103.2
88.0
8.3
71.2
58.2
45.2
8.3
89.4
76.4
63.4
8.2
107.6
94.6
81.6
8.2
116.5
110.1
97.1
8.2
112.6
112.6
101.9
8.3
79.7
64.6
49.4
8.3
99.6
84.5
69.3
8.2
119.5
104.3
89.2
8.2
120.3
117.1
106.2
8.2
116.3
116.3
111.4
8.3
88.2
70.9
53.7
8.3
109.8
92.5
75.3
8.2
131.4
114.1
96.9
8.2
124.1
124.1
115.3
8.2
119.9
119.9
121.0
8.3
117.7
99.1
80.5
8.3
136.4
122.2
103.5
8.2
126.3
126.3
122.0
8.2
122.1
122.1
122.6
8.3
125.7
105.7
85.7
8.3
141.4
130.2
110.2
8.2
128.6
128.6
128.6
8.2
124.3
124.3
124.3
105°F
10.2
56.2
45.6
34.9
9.9
74.6
63.8
53.1
9.7
93.0
82.1
71.4
9.5
94.6
92.9
82.3
10.2
65.1
50.3
37.6
10.0
82.5
69.8
57.1
9.8
100.0
89.4
76.7
9.5
97.3
96.2
89.9
9.6
97.9
97.9
91.0
10.3
74.0
54.9
40.3
10.1
90.5
75.8
61.2
9.8
106.9
96.7
82.0
9.6
100.1
99.5
97.4
9.7
100.6
100.6
97.4
10.4
82.9
59.6
43.0
10.1
98.4
81.8
65.2
9.9
113.9
104.0
87.4
9.7
102.8
102.8
105.0
9.7
103.4
103.4
103.8
10.2
105.3
87.4
69.5
9.9
115.8
109.5
93.1
9.7
104.5
104.5
105.6
9.7
105.1
105.1
105.3
10.2
112.2
93.0
73.7
9.9
117.7
114.9
98.8
9.7
106.2
106.2
106.2
9.8
106.8
106.8
106.8
Johnson Controls Unitary Products
75
70
65
-
-
-
46.5
-
-
63.0
52.1
-
77.1
66.2
55.3
-
-
-
50.4
-
-
68.5
55.5
-
84.1
71.1
58.0
88.9
75.8
62.8
-
-
-
54.2
-
-
74.1
58.9
-
91.1
75.9
60.8
96.3
81.1
66.0
-
-
-
58.0
-
-
79.6
62.3
-
98.0
80.8
63.5
103.7
86.4
69.2
61.8
-
-
84.9
66.3
-
103.3
84.7
66.0
104.0
85.4
66.7
65.6
-
-
90.2
70.2
-
108.6
88.6
68.6
104.3
84.3
64.2
-
-
-
42.4
-
-
60.6
49.9
-
71.6
60.8
50.1
-
-
-
44.5
-
-
64.0
51.3
-
77.2
64.5
51.8
78.3
65.6
52.9
-
-
-
46.5
-
-
67.4
52.7
-
82.8
68.1
53.5
82.7
68.1
53.4
-
-
-
48.6
-
-
70.8
54.2
-
88.4
71.8
55.2
87.2
70.6
54.0
51.5
-
-
75.2
57.2
-
87.6
69.7
51.8
87.4
69.4
51.5
54.5
-
-
79.5
60.3
-
86.9
67.6
48.4
87.5
68.3
49.0