  • Page 1 ® Relion 670 series Line differential protection RED670 ANSI Customized Product Guide...
  • Page 2: Table Of Contents

    22. Ordering.................99 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.
  • Page 3: Application

    1. Application High set instantaneous phase and ground overcurrent, four RED670 is used for the protection, control and monitoring of step directional or non-directional delayed phase and ground overhead lines and cables in all types of networks. The IED can overcurrent, thermal overload and two step under- and be used from distribution up to the highest voltage levels.
  • Page 4: Available Functions

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 2. Available functions Main protection functions = number of basic instances = option quantities IEC 61850 ANSI Function description Line Differential RED670 Differential protection HZPDIF 1Ph high impedance differential protection...
  • Page 5 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Back-up protection functions IEC 61850 ANSI Function description Line Differential RED670 Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC 51_67 Four step phase overcurrent protection EFPIOC Instantaneous residual overcurrent protection...
  • Page 6 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Line Differential RED670 Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser APC15 Apparatus control for single bay, max 15 apparatuses (2CBs) incl. interlocking...
  • Page 7 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 IEC 61850 ANSI Function description Line Differential RED670 SP16GGIO IEC61850 generic communication I/O functions 16 inputs MVGGIO IEC61850 generic communication I/O functions BSStatReport Logical signal status report RANGE_XP Measured value expander block...
  • Page 8 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Designed to communicate IEC 61850 ANSI Function description Line Differential RED670 Station communication SPA communication protocol LON communication protocol IEC60870-5-103 communication protocol 20/1 Operation selection between SPA and IEC60870-5-103 for SLM DNP3.0 for TCP/IP and EIA-485 communication protocol...
  • Page 9: Differential Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup...
  • Page 10 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 current differential protection with high sensitivity and provides Line differential protection, 3 or 6 CT sets L3CPDIF, L6CPDIF phase selection information for single-pole tripping. (87L) Line differential protection applies the Kirchhoff's law and...
  • Page 11 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protected zone Communication Channel Communication Channel Communication Channel ANSI05000040_2_en.vsd ANSI05000040 V2 EN Figure 2. Example of application on a three-terminal line with breaker-and-a-half breaker arrangements The current differential algorithm provides high sensitivity for...
  • Page 12 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 protection zone. Both two- and three-winding transformers are Line differential protection 3 or 6 CT sets, with in-zone correctly represented with phase shift compensations made in transformers LT3CPDIF, LT6CPDIF (87LT) the algorithm.
  • Page 13 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protected zone Communication Channel ANSI05000043_2_en.vsd ANSI05000043 V2 EN Figure 4. Five terminal lines with master-master system...
  • Page 14 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protected zone Communication Channels en05000044_ansi.vsd ANSI05000044 V1 EN Figure 5. Five terminal line with master-slave system Current samples from IEDs located geographically apart from The communication link is continuously monitored, and an...
  • Page 15: Impedance Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 The differential function can be allowed to trip as no load is fed • Startup element is sensitive enough to detect the abnormal through the line and protection is not working correctly.
  • Page 16 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 achieve. Therefore, FDPSPDIS (21) has a built-in algorithm for load encroachment, which gives the possibility to enlarge the resistive setting of both the phase selection and the measuring zones without interfering with the load.
  • Page 17 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Faulty phase identification with load encroachment FMPSPDIS (21) The operation of transmission networks today is in many cases close to the stability limit. Due to environmental considerations Operation area...
  • Page 18 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 achieve. Therefore, the function has a built in algorithm for load encroachment, which gives the possibility to enlarge the resistive setting of both the phase selection and the measuring zones without interfering with the load.
  • Page 19: Current Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 5. Current protection Directional operation can be combined together with corresponding communication logic in permissive or blocking Instantaneous phase overcurrent protection PHPIOC (50) teleprotection scheme. Current reversal and weak-end infeed The instantaneous three phase overcurrent function has a low functionality are available as well.
  • Page 20: Voltage Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Thermal overload protection, one time constant LPTTR Pole discordance protection CCRPLD (52PD) The increasing utilizing of the power system closer to the An open phase can cause negative and zero sequence currents...
  • Page 21: Frequency Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Two step overvoltage protection (OV2PTOV, 59) function can Underfrequency protection SAPTUF (81) is used for load be used to detect open line ends, normally then combined with shedding systems, remedial action schemes, gas turbine a directional reactive over-power function to supervise the startup and so on.
  • Page 22: Secondary System Supervision

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 CVGAPC can also be used to improve phase selection for high For better adaptation to system requirements, an operation resistive ground faults, outside the distance protection reach, mode setting has been introduced which makes it possible to for the transmission line.
  • Page 23 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 close first and the second will only close if the fault proved to function handles interlocking of one bay. The interlocking be transient. function is distributed to each IED and is not dependent on any central function.
  • Page 24: Scheme Communication

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 • fast clearance of faults is also achieved at the line end for AutomationBits, command function for DNP3.0 AUTOBITS which the faults are on the part of the line not covered by AutomationBits function for DNP3 (AUTOBITS) is used within its underreaching zone.
  • Page 25 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 The logic can be controlled either by the autorecloser (zone IED. To overcome these conditions, weak-end infeed (WEI) extension) or by the loss-of-load current (loss-of-load echo logic is used.
  • Page 26: Logic

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Features: length, as well as all functionality necessary for correct co- operation with autoreclosing functions. • Carrier redundancy to ensure security in DTT scheme • Blocking function output on CR Channel Error The trip function block also includes a settable latch •...
  • Page 27: Monitoring

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 an IED, either for forcing the unused inputs in other function • Trip value recorder blocks to a certain level/value, or for creating certain logic. • Disturbance recorder • Fault locator 13.
  • Page 28 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 The event recorder logs all selected binary input signals the Event function (EVENT). The event function block is used for connected to the Disturbance report function. Each recording remote communication.
  • Page 29: Metering

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 35-40 degrees apart the accuracy can be still maintained with the advanced compensation included in fault locator. 14. Metering Pulse counter logic PCGGIO Pulse counter (PCGGIO) function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy consumption values.
  • Page 30: Remote Communication

    An IED can communicate with up to 4 remote IEDs. SPA communication protocol A single glass or plastic port is provided for the ABB SPA Binary signal transfer to remote end, 192 signals protocol. This allows extensions of simple substation...
  • Page 31 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 enables extensive monitoring and evaluation of operation of the leased telephone lines. The module supports 64 kbit/s data IED and for all associated electrical circuits. communication between IEDs. Binary output module BOM...
  • Page 32 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 xx05000003.vsd IEC05000003 V1 EN Figure 11. 1/2 x 19” case with rear cover xx05000004.vsd IEC05000004 V1 EN Figure 12. Side-by-side mounting Case size 6U, 1/2 x 19” 10.47 8.81 7.92...
  • Page 33 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 • Wall mounting kit See ordering for details about available mounting alternatives.
  • Page 34: Connection Diagrams

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 20. Connection diagrams Table 1. Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X51...
  • Page 35 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 2. Designations for 3/4 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X101 and X102 X301:A, B, C, D...
  • Page 36 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 3. Designations for 3/4 x 19” casing with 2 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X71 and X301:A, B, C, D...
  • Page 37 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 4. Designations for 1/1 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X161 IOM or MIM and X162...
  • Page 38 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 5. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM and X132...
  • Page 39 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 6. CT/VT-input designation AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12 12I, 1A 12I, 5A 9I+3V, 1A 110-220V 110-220V 110-220V 9I+3V, 5A 110-220V 110-220V...
  • Page 40 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 1MRK002802-AB-11-670-1.2-PG-ANSI V1 EN Figure 15. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to rear position X32, X42, etc.
  • Page 41 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 1MRK002802-AB-8-670-1.2-PG-ANSI V1 EN Figure 20. IED with basic functionality communication interfaces...
  • Page 42: Technical Data

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 21. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified...
  • Page 43 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×...
  • Page 44 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Auxiliary DC voltage Table 11. PSM - Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20% EL = (90 - 250) V EL ±...
  • Page 45 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 13. BIM - Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ±...
  • Page 46 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage...
  • Page 47 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
  • Page 48 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 - 60 VDC 110 - 250 VDC...
  • Page 49 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC, DC...
  • Page 50 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 22. Frequency influence (reference standard: IEC 60255–1) Dependence on Within nominal range Influence Frequency dependence, operate value ± 2.5 Hz for 50 Hz ± 1.0% / Hz ± 3.0 Hz for 60 Hz Frequency dependence for distance protection operate value ±...
  • Page 51 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 24. Insulation Test Type test values Reference standard Dielectric test 2.0 kV AC, 1 min. ANSI C37.90 Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J Insulation resistance >100 MW at 500 VDC...
  • Page 52 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Differential protection Table 28. 1Ph High impedance differential protection HZPDIF (87) Function Range or value Accuracy Operate voltage (20-400) V ± 1.0% of I I=V/R Reset ratio >95% Maximum continuous power V>Pickup...
  • Page 53 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 30. Additional security logic for differential protection STSGGIO (11) Function Range or value Accuracy Operate current, zero sequence (1-100)% of lBase ±1,0% of I Operate current, low operation (1-100)% of lBase ±1,0% of I...
  • Page 54 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Impedance protection Table 31. Distance measuring zone, Quad ZMQPDIS (21) Function Range or value Accuracy Number of zones 5 with selectable direction Minimum operate residual (5-1000)% of IBase current, zone 1...
  • Page 55 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 32. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS (21) Function Range or value Accuracy Number of zones 5 with selectable direction IBase Minimum operate residual...
  • Page 56 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 34. Full-scheme distance protection, Mho characteristic ZMHPDIS (21) Function Range or value Accuracy Number of zones with selectable 5 with selectable direction directions Minimum operate current (10–30)% of I...
  • Page 57 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 36. Distance measuring zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS (21) Function Range or value Accuracy Number of zones 5 with selectable direction Minimum operate residual (5-1000)% of IBase...
  • Page 58 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 37. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS (21) Function Range or value Accuracy Minimum operate current (5-500)% of IBase Reactive reach, positive (0.50–3000.00) Ω/phase ± 2.0% static accuracy sequence ±...
  • Page 59 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 40. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase (10.0 - 100.0)% of VBase ± 0,5% of V and phase-to-neutral undervoltage Reset ratio, undervoltage <...
  • Page 60 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Current protection Table 42. Instantaneous phase overcurrent protection PHPIOC (50) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 61 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 44. Instantaneous residual overcurrent protection EFPIOC (50N) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 62 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 46. Four step negative sequence overcurrent protection NS4PTOC (46I2) Function Range or value Accuracy lBase Operate value, negative (1-2500)% of ± 1.0% of I at I £ I sequence current, step 1-4 ±...
  • Page 63 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 47. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) Function Range or value Accuracy lBase Operate level for 3I ·cosj (0.25-200.00)% of ± 1.0% of I at I £ I directional residual ±...
  • Page 64 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 47. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued Function Range or value Accuracy Operate time, non-directional 60 ms typically at 0 to 2 x I...
  • Page 65 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 49. Breaker failure protection CCRBRF (50BF) Function Range or value Accuracy lBase Operate phase current (5-200)% of ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio, phase current >...
  • Page 66 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 52. Directional underpower protection GUPPDUP (37) Function Range or value Accuracy SBase Power level (0.0–500.0)% of ± 1.0% of S at S < S ± 1.0% of S at S > S At low setting: (0.5-2.0)% of...
  • Page 67 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Voltage protection Table 55. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high step (1–100)% of VBase ± 0.5% of V Absolute hysteresis (0–100)% of...
  • Page 68 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 57. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy VBase Operate voltage, step 1 and step 2 (1-200)% of ± 0.5% of V at V < V ±...
  • Page 69 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 60. Loss of voltage check LOVPTUV (27) Function Range or value Accuracy Operate voltage (0–100)% of VBase ± 0.5% of V Pulse timer (0.050–60.000) s ± 0.5% ± 10 ms Timers (0.000–60.000) s...
  • Page 70 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Frequency protection Table 61. Underfrequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz Operate time, pickup function 100 ms typically...
  • Page 71 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 63. Rate-of-change frequency protection SAPFRC (81) Function Range or value Accuracy Operate value, pickup function (-10.00-10.00) Hz/s ± 10.0 mHz/s Operate value, internal blocking level (0-100)% of VBase ±...
  • Page 72 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Multipurpose protection Table 64. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input Phase A, Phase B, Phase C, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh,...
  • Page 73 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 64. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Reset time pickup undervoltage 25 ms typically at 0 to 2 x V High and low voltage limit, voltage dependent operation (1.0 - 200.0)% of VBase...
  • Page 74 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Secondary system supervision Table 65. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ± 10.0% of I at I > I...
  • Page 75 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Control Table 67. Synchronizing, synchronism check and energizing check SESRSYN (25) Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, V 0.500 - 2.000...
  • Page 76 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 68. Autorecloser SMBRREC (79) Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 1Ph (0.000-60.000) s ± 0.5% ± 10 ms...
  • Page 77 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Scheme communication Table 69. Scheme communication logic for distance or overcurrent protection ZCPSCH (85) Function Range or value Accuracy Scheme type Intertrip Permissive Underreach Permissive Overreach Blocking Co-ordination time for blocking (0.000-60.000) s...
  • Page 78 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 72. Current reversal and weak-end infeed logic for phase segregated communication ZC1WPSCH Function Range or value Accuracy Detection pickup phase to (10-90)% of VBase ± 0.5% of V...
  • Page 79 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Direct transfer trip Table 75. Low active power and power factor protection LAPPGAPC (37_55) Function Range or value Accuracy Operate value, low active power (2.0-100.0)% of SBase ± 1,0% of S Reset ratio, low active power <105%...
  • Page 80 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 79. Negative sequence overvoltage protection LCNSPTOV (47) Function Range or value Accuracy Operate value, negative sequence overvoltage (1-200)% of VBase ± 0.5% of V at V<V ± 0.5% of V at V>V Reset ratio, negative sequence overvoltage >95%...
  • Page 81 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 82. Zero sequence overcurrent protection LCZSPTOC (51N) Function Range or value Accuracy Operate value, zero sequence overcurrent (1-2500)% of IBase ± 1.0% of I at I<I ± 1.0% of I at I>I Reset ratio, zero sequence overcurrent >95%...
  • Page 82 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Logic Table 85. Tripping logic SMPPTRC (94) Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms Timers (0.000-60.000) s...
  • Page 83 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Monitoring Table 87. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Voltage (0.1-1.5) ×V ± 0.5% of V at V£V ± 0.5% of V at V > V Connected current (0.2-4.0) ×...
  • Page 84 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 91. Current sequence component measurement CMSQI Function Range or value Accuracy Current positive sequence, I1 (0.1–4.0) × I ± 0.2% of I at I ≤ 0.5 × I Three phase settings ±...
  • Page 85 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 95. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
  • Page 86 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 98. Indications Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances Table 99. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report...
  • Page 87 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Metering Table 102. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 103. Energy metering ETPMMTR...
  • Page 88 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Station communication Table 104. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 608–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
  • Page 89 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 109. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (3000ft/1000 m typically *)
  • Page 90 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Remote communication Table 113. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm Singlemode 9/125 µm...
  • Page 91 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Hardware Table 114. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 115. Water and dust protection level according to IEC 60529...
  • Page 92 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Basic IED functions Table 119. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 120. Time synchronization, time tagging...
  • Page 93 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 123. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 94 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Inverse characteristic Table 124. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷...
  • Page 95 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 125. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø...
  • Page 96 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 126. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 IEC 60255-151, 5% + 40 ×...
  • Page 97 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 128. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö VPickup V ç...
  • Page 98 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 129. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps 5% +40 ms of 0.01 æ ö...
  • Page 99: Ordering

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 22. Ordering Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections.
  • Page 100 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Optional functions Differential protection 1Ph High impedance differential protection (HZPDIF, 87) Qty: 1MRK 002 901-HB Additional security logic for differential protection (STSGGIO, 11REL) Qty: 1MRK 002 903-PA...
  • Page 101 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Impedance protection Rule: One and only one of the alternatives (Alt. 1-4) can be ordered Alternative 1: Rule: Distance protection and Directional impedance must be ordered together Note: Phase selection FDPSPDIS always included in this package)
  • Page 102 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Phase selection, quadrilateral characteristic with settable angle (FRPSPDIS, 21) Qty: 1MRK 002 925-XA Directional impedance quadrilateral (ZDRDIR, 21D) Qty: 1MRK 002 904-YB Note: Optional with alternative 1 Directional impedance element for mho characteristic (ZDMRDIR, 21D)
  • Page 103 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Current protection Instantaneous phase overcurrent protection (PHPIOC, 50) Qty: 1MRK 002 906-AC Four step phase overcurrent protection (OC4PTOC, 51/67) Qty: 1MRK 002 906-BD Instantaneous residual overcurrent protection (EFPIOC, 50N)
  • Page 104 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Frequency protection Underfrequency protection (SAPTUF, 81) Qty: 1MRK 002 908-NC Overfrequency protection (SAPTOF, 81) Qty: 1MRK 002 908-RC Rate-of-change frequency protection (SAPFRC, 81) Qty: 1MRK 002 908-SB Multipurpose protection...
  • Page 105 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Direct transfer trip Direct transfer trip (DTT) Qty: 1MRK 002 927-XA Station communication Note: Require 2-channel OEM IEC 62439-3 Edition 1 parallel redundancy protocol 1MRK 002 924-YR IEC 62439-3 Edition 2 parallel redundancy protocol...
  • Page 106 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Analog system Rule: One Transformer input module must be ordered Note: The same type of connection terminals has to be ordered for both TRMs Transformer input module, compression terminals...
  • Page 107 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Transformer input module, compression terminals 6I, 5A, 50/60 Hz Qty: 1MRK 002 247-DH Transformer input module, ring lug terminals 12I, 1A, 50/60 Hz Qty: 1MRK 002 247-CC Transformer input module, ring lug terminals...
  • Page 108 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Transformer input module, ring lug terminals 6I, 1A, 50/60 Hz Qty: 1MRK 002 247-DC Transformer input module, ring lug terminals 6I, 5A, 50/60 Hz Qty: 1MRK 002 247-DD Note: One Analog digital conversion module, with time synchronization is always delivered with each Transformer input module.
  • Page 109 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Binary input/output modules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 110 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Binary input module (BIM) with enhanced pulse counting capabilities, 16 inputs RL 24-30 VDC Qty: 1MRK 000 508-HA 10 11 12 13 RL 48-60 VDC Qty: 1MRK 000 508-EA...
  • Page 111 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 112 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Station communication ports Note: Optical ethernet module, 2 glass interfaces is not allowed together with SLM. Optical ethernet module, 1 channel glass 1MRK 002 266-AA Optical ethernet module, 2 channel glass 1MRK 002 266-BA Serial and LON communication module, supports SPA/IEC 60870-5-103, LON and DNP 3.0...
  • Page 113 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Flush mounting kit for terminal Quantity: 1MRK 000 020-Y Flush mounting kit + IP54 sealing (factory mounted). Cannot be ordered separately thus must be Quantity: 1MRK 002 420-EA specified when ordering a terminal.
  • Page 114 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protection cover Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC Protective cover for rear side of terminal, 6U, 3/4 x 19”...
  • Page 115 Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Rule: Specify additional quantity of IED Connect CD requested . Quantity: 1MRK 002 290-AB Rule: Specify the number of printed manuals requested Operator’s manual ANSI Quantity: 1MRK 505 223-UUS...
  • Page 116 670 series SPA and signal list 1MRK 500 092-WUS IEC 61850 Data objects list for 670 series 1MRK 500 091-WUS Engineering manual 670 series 1MRK 511 240-UUS Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 118 ABB Inc. 3450 Harvester Road Burlington, ON L7N 3W5, Canada Phone Toll Free: 1-800-HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc. 53125, Naucalpan, Estado De Mexico, MEXICO Phone (+1) 440-585-7804, menu...