PG-D2
The terminal specifications for the PG-D2 are given in Table 2.20.
Terminal
No.
1
2
3
4
TA1
5
6
7
8
TA2
(E)
* 5Vdc and 12Vdc cannot be used at the same time.
Wiring the PG-D2
Wiring examples are provided in Fig 2.21 for the PG-D2.
Branch
R/L1
Circuit
S/L2
Protection
T/L3
Tel: +(86) 755 8660 6182
Table 2.20 PG-D2 Terminal Specifications
Contents
Power supply for pulse generator
Pulse input terminals
Common terminal
Pulse monitor output terminals
Shield connection terminal
Drive
4CN
•
Shielded twisted-pair wires must be used for signal lines.
•
Do not use the PG-D2's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
•
The length of the pulse generator's wiring must not be more than 100 meters.
Electrical Installation 2 - 36
Aotewell
12Vdc (±5%), 200mA max.*
0Vdc (GND for power supply)
5Vdc (±5%), 200mA max.*
Line driver input (RS-422 level)
Maximum response frequency: 300kHz
Line driver output (RS-422 level)
4CN
Fig 2.21 PG-D2 Wiring
Aotewell
Email: Sales@aotewell.com
Specifications
-
-
Power supply +12Vdc
Power supply 0Vdc
Power supply +5Vdc
Pulse input + (A phase)
Pulse input - (A phase)
Pulse monitor output
http://www.aotewell.com