2. Cooling System
Use only automotive grade antifreeze and distilled water in cooling system.
Do not use water that contains salt or alkalis (Tap Water)! Using non-distilled
water creates scale in the radiator, causing corrosion and premature wear.
You must check and maintain all fuel, lubricant and coolant levels. Not doing so will accelerate and shorten the
life of the standby system. Attention must be paid to all fluid systems and annually serviced by an authorized
service provider or call 844-367-5660 for assistance.
Converting from Natural Gas (NG) to Liquid Propane Gas (LPG)
Most generators are configured for natural gas operation at the factory. Switching over to LP Vapor is a simple
procedure.
3. Fuel Conversion
Do not touch hot engine parts. The engine and exhaust system components
become extremely hot during operation.
Two fuel connections on the fuel block allow field conversion between natural gas (NG) and Liquid Propane
(LPG). The fuel metering valves are factory-set and sealed to provide the best possible hot and cold starting.
Use the following procedure to convert fuel from type to another.
Natural Gas (NG) and Liquid Propane (LPG) Conversion.
• Use a pressure reducing valve to reduce LP pressure supply as needed.
• Push or pull the pin located above Regulator as pictured below, for desired fuel type.
A. Liquid propane (LPG)
For engines set up to run on Liquid propane, please check the fuel supply pressure, lower or higher
pressure range will result in equipment failure. Inlet pressure 1.7kPa to 3.5kPa, and gas line should be no
longer than 16 feet or 5 meters, the inner diameter shall not be less than (0.63") or 16mm.
It is strictly prohibited to remove high pressure gas lines during operation,
service and repair. Contact your service provider. You must check and test for
gas leaks using a gas leak detector before use. The observation time is not
less than 1 minute per connection. Based on different gas sources that are available, there may be different
gas pressures present. Make sure pressure is known before installation. A pressure reducing valve may be re-
quired to obtain optimal requirements. You will need to use a pressure reducing valve if the pressure is exces-
sively high. Additional parts and tools such as leak detectors and pressure gauges are not included with this
purchase.