Technology modules

PLCSIM Advanced simulates the real CPU, but not configured, connected technology
modules or other I/O devices.
It is possible to download a project with technology modules for operation of motion control.
However, the built-in logic of the technology modules is not part of the simulation, which is
why the associated Motion Control instructions are not supported.
Additional information
For more information on Motion Control, refer to the following manuals:
● Device manuals to support SIMATIC controllers
(https://support.industry.siemens.com/cs/ww/en/view/109744173)
● Function manual S7-1500 Motion Control
(https://support.industry.siemens.com/cs/ww/en/view/109739589)
● Function manual S7-1500T Motion Control
(https://support.industry.siemens.com/cs/ww/en/view/109481326)
8.9.3
OB 91 and OB 92
If you convert a Motion Control project which contains the OB 91 and OB 92 from
STEP 7 V13, then you cannot load this project to a PLCSIM Advanced.
Remedy
Delete OB 91 and OB 92 in the project and recompile the project.
The OBs are thus created again with the simulation support required for PLCSIM Advanced.
Compilation resets the properties of the blocks to the default values.
Restore the required settings in the properties.