Multiple Outdoor Unit Installation; Outdoor Unit Installation In Multi Row - Fujitsu AB*G45LRTA series Design & Technical Manual

Ceiling type
Hide thumbs Also See for AB*G45LRTA series:
Table of Contents

Advertisement

4-2.

MULTIPLE OUTDOOR UNIT INSTALLATION

WHEN THE UPWARD AREA IS OPEN
Obstacles at rear only
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA
Obstacles at rear and above only
4-3.

OUTDOOR UNIT INSTALLATION IN MULTI ROW

Single parallel unit arrangement
1000
If the space is larger than stated, the condition will be the same as those without any obstacles.
Obstacles at front only
300
1500
150
2000 or more
600
- (02 - 06) -
Obstacles at front and rear
only
1500 or more
1500
500
Max. 300
Multiple parallel unit arrangement
1500
(Unit : mm)
500
1500 or more
(Unit : mm)
(Unit : mm)
500
3000 or more
600