ELECTRICAL
UNIT
CHARACTERISTICS
50HS048
208/230-1-60, 208/230-3-60, 460-3-60
50HS060
208/230-1-60, 208/230-3-60, 460-3-60
REQ'D CLEARANCES FOR SERVICING — in. (mm)
Indoor Coil Access Side . . . . . . . . . . . . . . . . . 30 (762)
Control Box Access Side . . . . . . . . . . . . . . . . 30 (762)
(Except for NEC requirements)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side Opposite Ducts . . . . . . . . . . . . . . . . . . 30 (762)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L — in. (mm)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . 0
Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . 0
Vertical Discharge, First 12 in. (305) of Supply Duct
UNIT WT
Lb
Kg
379
172
393
179
. . . 1 (25)
Fig. 5 — Dimensions; Sizes 048,060; With Optional Base Rail
CORNER WT (Lb/Kg)
A
B
C
D
94/43
86/39
118/54
81/37
97/44
90/41
121/55
85/39
NEC REQ'D CLEARANCES — in. (mm)
Between Units, Control Box Side . . . . . . . . . . . 42 (1067)
Unit and Ungrounded Surfaces, Control Box Side . . . .36 (914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . . . . . . 42 (1067)
LEGEND
CG
— Center of Gravity
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required
NOTE: Clearances must be maintained to prevent
recirculation of air from outdoor-fan discharge.
5
CENTER OF GRAVITY (in./mm)
UNIT
X
Y
50HS048
19.6/498
20.6/524
50HS060
19.6/497
20.6/524
Z
17.3/440
17.3/440