Analog inputs/outputs X482
Table 4- 3
Terminal strip X482
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 0.5 mm
AI: Analog input, AO: Analog output
1)
Note
An open input is interpreted as approximately "0 V".
The power supply of the analog inputs/outputs is drawn via the option slot of the Control Unit
and not via X424.
The shield is connected to the Control Unit.
CAUTION
The common-mode range must not be violated.
The analog differential voltage signals can have a maximum offset voltage of +/-30 V with
respect to the ground potential. If the range is violated, incorrect results may occur during
analog/digital conversion.
Terminal Board 30 (TB30)
Operating Instructions, 03/2012, A5E01221269A
Designation
1)
AI 0+
AI 0-
AI 1+
AI 1-
AO 0+
AO 0-
AO 1+
AO 1-
2
Technical data
Analog inputs (AI)
Voltage: -10 V to +10 V
Inner flow resistance: 65 kΩ
Resolution: 13 bit + sign
Analog outputs (AO)
Voltage range: -10 V to +10 V
Load current: max. -3 mA to +3 mA
Resolution: 11 bit + sign
Continuously short-circuit proof
Electrical installation
17