Transceiver error codes

Error
Description
code
01
System error
Prohibited action
11
Checksum error
21
31
EEPROM data read error
EEPROM data write error
32
Low temperature
41
42
High temperature
Too low field probe current
51
Too high field probe current
52
14
Suggested cause and action
Turn off the transceiver and re-start. If the error
persists, a serious internal fault has occurred with
the Transceiver. Contact your
EXCOUNT-II service representative.
The user has attempted to do something which is prohibited.
An error occurred in the data transmission and the data
has been lost or corrupted. Interference from a nearby
cellular/mobile phone can be a likely cause. Try to re-transmit
the data.
The transceiver could not read from the internal EEPROM
memory. Turn off the transceiver and re-start. If the error
persists, contact your EXCOUNT-II service representative.
The transceiver could not write to the internal EEPROM
memory. Turn off the transceiver and re-start. If the error
persists, contact your EXCOUNT-II service representative.
The ambient temperature is lower than defined in the data-
base for resistive current measurements. (Lowest defined
temperature is -10 º C). Take new measurements at another
time.
The ambient temperature is higher than defined in the data-
base for resistive current measurements. (Highest defined
temperature is +60 º C). Take new measurements at another
time.
The system voltage is too low to generate sufficient current in
the field probe in the sensor. Check that the line is correctly
energised.
The system voltage is too high. Check that the line is cor-
rectly energised.
2501en EXCOUNT-II Users Manual