Alternate Method Of Providing Air From Outside; Air From Inside - Nordyne SC038D-23A Installation Instructions Manual

Single stage condensing furnaces 92.1% afue
Table of Contents

Advertisement

Alternate Method of Providing Air from Outside:

If acceptable under local Codes, it is permitted to
provide outside air using one opening (See NFGC).
Generally, confi ned spaces must have two openings
in the space for combustion air. One opening must
be within 12 inches of the ceiling, and the other
must be within 12 inches of the fl oor. However, an
alternative method recently adopted by the NFGC
uses one opening within 12 inches of the top of the
space. This method may be used if it is acceptable
to the local codes.
The following conditions must be met:
1. The opening must start within 12" of the top of the
structure and connect with the out of doors through
vertical or horizontal ducts or be ducted to a crawl
or attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1
sq. in. per 3,000 Btu per hour of the total input rating
of all equipment located in the enclosure.
3. The free area must not be less than the sum of all
the areas of the vent connectors in the enclosure.
Vent or
Chimney
Outlet
Air
Furnace
Inlet Air
Alternate
Air Inlet
Ventilation Louvers For
Unheated Crawl Space
Figure 3. Combustion Air Drawn from a Crawl
Space or Vented Attic

Air From Inside

If combustion air is taken from the heated space, the two
openings must each have a free area of at least one square
inch per 1,000 Btuh of total input of all appliances in the
confi ned space, but not less than 100 square inches of
free area (Figure 5). For example, if the combined input
rate of all appliances is less than or equal to 100,000
Btuh, each opening must have a free area of at least 100
square inches. If the combined input rate of all appliances
is 120,000 Btuh, each opening must have a free area of
at least 120 square inches.
Ventilation Louvers
(each end of attic)
NOTE: Air openings shall
each have a free area of
Water
not less than one square
Heater
inch per 4,000 Btuh of the
total input rating of all
equipment in the enclosure.
Vent or
Chimney
- - -
See
- - -
- - -
12"
Note
Water
Max
Heater
See
Note
- - -
12" Max.
- - -
- - -
Total Input Rating
Minimum Free Area
(Btuh)
(Each Opening)
40,000
60,000
80,000
100,000
120,000
140,000
160,000
Figure 4. Combustion Air Drawn from Outside
Through an Exterior Wall
Vent or
Chimney
NOTES:
Each opening must be
at least 100 sq. in. or
1 sq. in. per 1,000 Btuh
of total input rating,
whichever is greater.
Openings must start at
no more than 12 inches
from the top and bottom
of the enclosure.
Total Input Rating
Minimum Free Area
(Btuh)
(Each Opening)
40,000
60,000
80,000
100,000
120,000
140,000
160,000
Figure 5. Combustion Air Drawn from Inside
Furnace
Round Duct
Diameter
10 sq. In
4 inches
15 sq. In
5 inches
20 sq. In
5 inches
25 sq. In
6 inches
30 sq. In
6 inches
35 sq. In
7 inches
40 sq. In
8 inches
12" Max.
Water
Heater
Furnace
See
Notes
12" Max.
Round Duct
Diameter
100 sq. In
12 inches
100 sq. In
12 inches
100 sq. In
12 inches
100 sq. In
12 inches
120 sq. In
13 inches
140 sq. In
14 inches
160 sq. In
15 inches
See
Notes
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents