Refrigeration Cycle Diagram - LG LM-4462C2T Service Manual

Ceiling cassette multi
Table of Contents

Advertisement

Refrigeration Cycle Diagram

LM-4462H2T
INDOOR A-UNIT
CAPI
HEAT
EXCHANGER
INDOOR B-UNIT
CAPI
HEAT
EXCHANGER
Pipe size(Diameter: ø)
Gas
Liquid
5/8"
( Rated performance for refrigerant line length of: 7.5m)
For installation over rated distance, 70g of refrigerant should be added for each meter in Heat pump Model.
For installation over rated distance, 50g of refrigerant should be added for each meter in Cooling only Model.
ex) When installed at a distance of 15m, 525g of refrigerant should be added in Heat pump Model.
(15-7.5) x 70g = 525g
When installed at a distance of 15m, 375g of refrigerant should be added in Cooling only Model.
(15-7.5) x 50g = 375g
LIQUID SIDE
GAS SIDE
GAS SIDE
LIQUID SIDE
Rated
3/8"
7.5
A-COMPRESSOR
B-COMPRESSOR
Piping length(m)
Max.
50
–7–
OUTDOOR UNIT
CAPILLARY TUBE
A-REVERSING
VALVE
B-REVERSING
VALVE
CAPILLARY TUBE
Elevation(m)
Rated
7.5
HEAT
EXCHANGER
HEAT
EXCHANGER
COOLING
HEATING
Max.
30