Electrical connections
4.5.1

Electrical connection of TZIDC for remote position sensor

1
2
3
Fig. 23: TZIDC control unit
1 Analog position feedback
2 Digital position feedback switch 1
3 Digital position feedback switch 2
4 Connecting cable for remote position sensor
5 Connecting cable for remote position sensor
6 Connecting cable for remote position sensor
IMPORTANT (NOTE)
Connect the connecting cable shield to both housings using EMC cable glands.
If the control unit is attached so that it is it non-conductive, the housing must be grounded
(control unit and remote sensor housing at same electrical level); otherwise control deviations
could occur with regard to analog position feedback.
The pneumatic outputs must be connected to the drive using cables at least 6 mm in diameter.
28
4
5
6
7
8
9
10
7 Binary output
8 Binary input
9 Setpoint input
10 Ground connection
11 Remote position sensor
TZIDC, TZIDC-110, TZIDC-120
11
M00760
CI/TZIDC/110/120-EN