7.1.5
IECEx n
Electrical data
Signal circuit
(terminal +11 / -12)
Contact input
(terminal +81 / -82)
Switch output
(terminal +83 / -84)
The following modules may be operated with the TZIDC as an option:
Plug-in module for digital position feedback
(terminal +51 / -52 or +41 / -42)
Plug-in module for analog position feedback
(terminal +31 / -32)
Plug-in module for shutdown contact input
(terminal +51 / -52 or +85 / -86)
Mechanical digital feedback
(terminal limit1 +51 / -52 or limit2 +41 / -42)
Special conditions
•
Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
•
For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
•
It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
•
Only non-flammable gases may be used for the pneumatic auxiliary power.
•
Only use suitable cable entries which meet the requirements of IEC 60079-15.
•
If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
7.1.6
CSA International
Certificate:
Class 2258 02
Class 2258 04
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X:
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
Ex relevant specifications
U = 9.7 V DC
I = 4 ... 20 mA, max. 21.5 mA
U = 12 ... 24 V DC; 4 mA
U = 11 V DC
U = 5 ... 11 V DC
U = 10 ... 30 V DC
I = 4 ... 20 mA, max. 21.5 mA
U = 20 ... 30 V DC
U = 5 ... 11 V DC
1052414
PROCESS CONTROL EQUIPMENT –
For Hazardous Locations
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
41